APC UPS Manager

A Python desktop application for monitoring and configuring APC Smart-UPS units via the UPS-Link serial protocol. Connects over RS-232 (or USB-serial adapter) at 2400 baud and provides real-time monitoring, full EEPROM setting management, register diagnostics, and service-level calibration tools.

Built as a modern, open-source replacement for the legacy APCfix.exe utility, with a safety-first design that prevents accidental changes to critical UPS parameters.

Sources and Credits

  • APCfix.exe — The original DOS/Windows UPS configuration tool that inspired this project. APCfix provided direct EEPROM access and register viewing for APC Smart-UPS units. This project replicates and extends its capabilities in a modern Python GUI.

  • UPS-Link Protocol Specification (UPS-Link_Protocol_Specification.pdf) — APC's official protocol document covering all serial commands, response formats, register bit maps, and EEPROM editing procedures.

  • APC Smart-UPS XL Manual (apc-sua2200xli-ups-manual.pdf) — Hardware reference manual for the Smart-UPS 2200 XL (SUA2200XL-I).

  • Community field-service guide — Originally published at ebastlirna.cz (Czech electronics forum). Contains undocumented service procedures, PROG mode details, smart battery constants, and field calibration techniques that are not covered in APC's official documentation. Translated and adapted in field_service_notes.md.

  • Serial cable pinout (att_124.jpg) — Wiring diagram for the APC 940-024C serial cable.

Requirements

  • Python 3.10+
  • pyserial >= 3.5
  • tkinter (included with most Python installations)
  • RS-232 serial connection to the UPS (direct or via USB-serial adapter)
pip install -r requirements.txt

Running

python run.py

Project Structure

APC-UPS/
├── run.py                          Entry point
├── requirements.txt                Dependencies (pyserial)
├── field_service_notes.md          Community service guide (from ebastlirna.cz)
├── apc_ups/
│   ├── protocol/
│   │   ├── constants.py            Baud rate, timing, alert chars, register bit maps
│   │   ├── commands.py             Command registry (50+ UPS commands)
│   │   ├── serial_conn.py          Thread-safe pyserial wrapper
│   │   └── ups_protocol.py         Command send/receive, async alert filtering
│   ├── core/
│   │   ├── ups_manager.py          High-level orchestrator (connect, poll, settings)
│   │   ├── ups_state.py            Data model for all UPS values
│   │   ├── editable_settings.py    13 editable settings with allowed values
│   │   └── calibration.py          Battery runtime calibration state machine
│   ├── ui/
│   │   ├── app.py                  Main window, port selector, tab management
│   │   ├── main_tab.py             Monitor tab (live readings, action buttons)
│   │   ├── settings_tab.py         Settings tab (EEPROM editing)
│   │   ├── status_tab.py           Registers & Log tab (diagnostics)
│   │   ├── service_tab.py          Service Tools tab (PROG mode, calibration)
│   │   ├── dialogs.py              Three-tier confirmation dialogs
│   │   └── tooltip.py              Hover tooltip system
│   └── util/
│       ├── register_decoder.py     Hex register to bit flag decoding
│       └── port_scanner.py         Serial port enumeration
└── tests/
    ├── test_protocol.py            Protocol and mock UPS tests
    ├── test_register_decoder.py    Register decoder tests
    ├── test_editable_settings.py   Setting definitions and edit cycling tests
    └── mock_ups.py                 Simulated UPS for testing without hardware

Application Guide

Connection Bar

Element Description
Serial Port dropdown Lists all detected serial/COM ports on the system.
Scan Ports button Re-scans for serial ports. Use after plugging in a USB-serial adapter.
Connect button Opens the selected port, enters Smart Mode (Y command), and reads all UPS values.
Disconnect button Stops monitoring and closes the serial connection.

Status Bar

The bottom bar shows three pieces of information:

  • Connection state — "Disconnected", "Connecting to COMx...", or "Connected"
  • UPS model — Model name reported by the UPS (bold)
  • Line status — "On Line" or "ON BATTERY"

Monitor Tab

The main monitoring tab with live readings updated every 2 seconds.

Left Panel — UPS Identity

Field Description
Model UPS model name (read via Ctrl+A command).
Firmware 3-character firmware code: model type, revision, voltage class.
Manufactured Date the UPS was manufactured (from EEPROM).
Battery Replaced Date batteries were last replaced. Editable in the Settings tab.
UPS Name 8-character user-assigned identifier. Editable in the Settings tab.
Serial Number Factory serial number (read-only).
Line Frequency Measured AC line frequency in Hz. Polled every ~10 seconds.
Internal Temp Internal UPS temperature in Celsius. Polled every ~10 seconds.
Battery System Nominal battery system voltage (e.g. 24V, 48V).

Center Panel — Live Readings

Element Description
Firmware & Battery Constants Firmware version detail and the four undocumented smart constants (0, 4, 5, 6) that control battery discharge curve estimation.
Temperature Alert Banner Red banner that appears when internal temperature exceeds the configured threshold (default 40 C).
Battery Age Warning Gold banner that appears when battery age exceeds 2 years, suggesting replacement.
Estimated Runtime Minutes of battery runtime remaining at the current load level. Polled every ~10 seconds.
Battery Charge Level Progress bar and percentage showing remaining battery capacity. Must be 100% to start runtime calibration.
Output Load Vertical progress bar showing load as percentage of rated capacity, plus estimated watts. Bar changes color from green to yellow to red as load increases.
Input Voltage Vertical progress bar and value (0-300V scale) showing measured AC input voltage. Polled every ~2 seconds.
Output Voltage Measured AC output voltage to connected equipment. Polled every ~2 seconds.

Right Panel — Voltage and Battery Details

Field Description
Battery Voltage Present DC battery voltage.
Battery Packs Number of external battery packs connected (0-255). Affects runtime calculation.
Upper Transfer Input voltage above which the UPS transfers to battery.
Lower Transfer Input voltage below which SmartBoost engages.
Output Setting Nominal output voltage when running on battery.
Peak Input Maximum input voltage recorded since last poll. Resets each time it is read.
Lowest Input Minimum input voltage recorded since last poll. Resets each time it is read.

Action Buttons

Button Description
Run Battery Test Runs an automatic battery self-test (~8 seconds). The UPS briefly switches to battery power and back. Result appears in the Registers & Log tab.
Test Indicators Flashes all front-panel LEDs and sounds the beeper for about 2 seconds. Safe diagnostic check.
Toggle Bypass Switches between normal and bypass mode. In bypass mode, the load is fed directly from mains — the UPS is NOT protecting connected equipment.
Meter Comparison Opens a dialog to compare UPS voltage readings against an external voltmeter. Enter your meter readings for input, output, and/or battery voltage to see the delta.

Transfer Cause

Displays the reason the UPS last transferred to battery power:

Code Meaning
R Unacceptable utility voltage rate of change
H High utility voltage
L Low utility voltage
T Line voltage notch or spike
O No transfers have occurred
S UPS-Link command or self-test

Settings Tab

Left Panel — UPS Identity (Read-Only)

Displays the same identity fields as the Monitor tab (model, firmware, serial number, etc.) plus a safety warning that all setting changes are written to EEPROM and take effect immediately.

Right Panel — Editable Settings

Each setting is shown as a row with the current value and a Change button. Clicking Change opens a confirmation dialog appropriate to the setting's danger level.

Setting Command Allowed Values Danger Level
Low Battery Warning q 02, 05, 07, 10 minutes Normal
Shutdown Delay p 020, 180, 300, 600 seconds Caution
Turn On Delay r 000, 060, 180, 300 seconds Caution
Self-Test Interval E 336 hrs, 168 hrs, On startup, Off Normal
Min Battery for Restart e 0%, 15%, 50%, 90% Caution
Sensitivity s High, Medium, Low Caution
Alarm Control k Immediate, 30s delay, Low battery only, Disabled Normal
Upper Transfer Voltage u 253, 264, 271, 280 V Caution
Lower Transfer Voltage l 196, 188, 208, 204 V Caution
Output Voltage Setting o 220, 225, 230, 240 V Caution
Battery Packs > 0-255 (direct numeric input) Caution
UPS ID c 8-character free text Normal
Battery Replacement Date x Date in dd/mm/yy format Normal

Factory Reset Settings

Resets ALL UPS EEPROM settings to factory defaults. Transfer voltages, sensitivity, delays, alarms, and self-test interval are all reverted. UPS ID and battery date are NOT affected. Requires typing "YES" to confirm (Dangerous tier).


Registers & Log Tab

Register Panels

Four panels of read-only checkboxes showing the decoded bits of each UPS register. Registers are refreshed during normal polling.

State Register (~) — Bypass and ready states:

  • In Wakeup mode
  • Ready to power load
  • In bypass (manual / UPS-Link / internal fault)
  • Returning from bypass
  • Going to bypass
  • Ready on return of line power

Trip1 Register (') — Fault conditions causing bypass:

  • Bad output voltage
  • SmartBoost/SmartTrim relay fault
  • Bypass supply failure
  • DC imbalance
  • Output voltage select failure
  • Fan failure (electronics unit / isolation unit)

Trip Register (8) — Critical faults:

  • Temperature exceeded
  • Bypass relay malfunction
  • Battery charger failure
  • In shutdown mode
  • In sleep mode
  • Main relay malfunction
  • Overload on battery failure
  • Low battery shutdown

Status Register (Q) — Current operating state:

  • Replace Battery
  • Battery Low
  • Overloaded Output
  • On Battery
  • On Line
  • SmartBoost active
  • SmartTrim active
  • Runtime calibration occurred

Event Log

Dark-background scrolling log with green text showing timestamped messages and asynchronous UPS alerts. Alerts include:

Alert Meaning
! Line Fail — UPS transferred to battery
$ Return from Line Fail — back on line power
% Low Battery — capacity critically low
+ Return from Low Battery — battery recharged
? Abnormal Condition — UPS fault
= Return from Abnormal Condition — fault cleared
* About to Turn Load Off — imminent shutdown
# Replace Battery — battery needs replacement
& Check Alarm Register — refer to Trip/Trip1 registers
| EEPROM Variable Change — a setting was modified

Service Tools Tab

Advanced tools for field service technicians. A warning banner reminds that incorrect calibration can damage equipment.

PROG Mode (Voltage Calibration)

An undocumented APC service mode that allows fine-tuning the internal voltage measurement calibration stored in EEPROM. The workflow is: Enter PROG > Select measurement > Read > Nudge +/- > Save > Exit.

Element Description
Measurement selector Choose which voltage to calibrate: L (Input), O (Output), or B (Battery).
Current Reading Displays the UPS voltage reading in PROG mode. Compare against an external voltmeter.
Enter PROG Enters PROG mode. Sends "1", waits 4 seconds, sends "1" again. Polling pauses.
Nudge + Increases the calibration value by one step.
Nudge - Decreases the calibration value by one step.
Read Reads the current voltage value for the selected measurement type.
Save to EEPROM Writes the adjusted calibration value to EEPROM permanently. Sends the "R" (Record) command.
Exit PROG Exits PROG mode (sends ESC). Unsaved changes are discarded. Polling resumes.

Temperature Monitoring

Element Description
Current temperature Internal UPS temperature in Celsius.
Alert threshold Temperature above which a red warning banner appears on the Monitor tab. Default is 40 C. Session-only setting (not stored on UPS).
Apply Threshold Applies the entered threshold value.
Temperature history Session statistics: reading count, average, minimum, and maximum temperature since connection. Keeps up to 360 readings (~1 hour at 10-second intervals).

Runtime Calibration Pre-Check

Displays values that should be reviewed before starting a runtime calibration (D command):

Field Description
Constant 0 (Runtime) Battery discharge curve runtime constant. Should be at factory default before calibrating. A warning appears if it differs.
Constant 4 (Low) Discharge curve parameter (low range). Factory-set.
Constant 5 (Mid) Discharge curve parameter (mid range). Factory-set.
Constant 6 (High) Discharge curve parameter (high range). Factory-set.
Battery status Shows current charge percentage and whether the battery is ready for calibration (must be 100%).

Safety Model

All write operations use a three-tier confirmation system to prevent accidental changes.

Normal (Green)

Simple "Are you sure?" dialog with Cancel and Apply buttons. Used for low-risk operations:

  • Self-test, LED/alarm test
  • UPS ID change, battery date change
  • Self-test interval, alarm control

Caution (Yellow)

Yellow warning banner: "CAUTION: This changes UPS behavior." Cancel button is focused by default. Used for settings that affect UPS protection behavior:

  • Transfer voltages (upper/lower)
  • Sensitivity, shutdown delay, wake-up delay
  • Minimum battery for restart, output voltage
  • Battery packs

Dangerous (Red)

Red warning banner with a text field requiring the user to type "YES" before the Execute button enables. Used for:

  • Factory reset (EEPROM wipe)
  • Runtime calibration
  • Shutdown commands (K..K, Z..Z, S)

Additional Safeguards

  • No keyboard shortcuts for write operations — all require mouse clicks
  • All Change buttons are disabled while a setting change is in progress
  • All write operations are logged with timestamp in the Event Log
  • Polling pauses automatically during any write operation to prevent bus contention

Protocol Details

  • Baud rate: 2400, 8N1, no flow control
  • Smart Mode: Send Y → expect SM\r\n
  • Commands: Single ASCII character, responses terminated with \r\n
  • Async alerts: Single character (! $ % + ? = * # & |), no terminator
  • Timed commands (K, Z): Two identical characters with >1.5 second delay between them
  • Edit cycling: Send command char to read current value, then - to advance EEPROM to next value in the allowed set
  • Direct edit (c, x): Send command, -, then type 8 characters, expect OK
  • PROG mode: Send 1, wait 4 seconds, send 1 → expect PROG. Use +/- to adjust, R to save, ESC to exit.

Testing

Run the test suite (46 tests):

python -m unittest discover -s tests -v

Tests cover:

  • Protocol command encoding and response parsing
  • Mock UPS simulation (Smart Mode, commands, edit cycling, PROG mode)
  • Register bit decoding (status, state, trip, trip1)
  • Editable setting definitions, allowed values, and edit cycle counting
  • Smart constants and PROG mode sequences
  • Battery age computation and calibration pre-checks

Known Issues

  • CH340 USB-serial adapter reconnection: After using the Disconnect button, clicking Connect again may fail with PermissionError(13, 'A device attached to the system is not functioning.'). This is a Windows driver issue where the CH340 chipset does not fully release the COM port after close. Workaround: Unplug and re-plug the USB-serial adapter, then click Connect. Other USB-serial chipsets (FTDI, CP2102) are not known to have this issue.

  • Factory Reset does not reset Battery Packs: The z (EEPROM reset) command does not appear to reset the external battery packs count. This is a UPS firmware limitation — the battery packs value may be stored in a separate EEPROM region. Set the battery packs count manually via the Settings tab after a factory reset.


License

This project is provided as-is for personal and educational use. The UPS-Link protocol specification is proprietary to APC/Schneider Electric.