APC Smart-UPS Field Service Notes

Source: Community field-service guide originally published at ebastlirna.cz (Czech electronics forum). Translated and adapted for reference here.

Findings from community and field-service documentation, cross-referenced against our application's current capabilities. This document is intended as a practical reference for anyone maintaining APC Smart-UPS units with our software.


1. Battery Life and Temperature Effects

Community Findings

Condition Internal Temp Expected Battery Life
Open desk, 25 C room 34--36 C ~6 years
Open desk, 35 C ambient (or enclosed cabinet) ~45 C ~1.5 years
Enclosed cabinet in summer >50 C <1 year

Key observations:

  • Battery life halves for every 10 C increase above 25 C.
  • At 45 C and above, battery brand is irrelevant --- all fail within two years.
  • An 80x80x40 mm Sunon fan (15--20 W) reduced idle temperature from 34--36 C down to 24--26 C, and limited battery-discharge temperature rise to 2 C (versus 46 C without cooling).
  • Fan should be powered from UPS input (mains side), not the UPS output, to avoid draining the battery during an outage.

Application Support

Capability Status Detail
Read internal temperature (C command) Supported Polled every ~10 s (slow poll). Displayed in the UI as temperature.
Temperature trend / logging Supported Session-based history (up to 360 readings, ~1 hour at 10s intervals). Min/max/average summary shown in Service tab.
High-temperature alert Supported Configurable threshold (default 40 C) in Service tab. Red warning banner in main tab when exceeded. Alert logged to status messages.
Battery age tracking Supported The battery_replace_date (x command) is editable. Users can record the date batteries were last replaced.

Potential Enhancements

  • Add a configurable high-temperature warning threshold (e.g., alert if C > 40 C).
  • Add persistent temperature logging so users can identify enclosure heat problems before batteries are damaged.
  • Surface a "battery age" indicator computed from battery_replace_date and the temperature history, so users get a proactive replacement reminder.

2. Voltage Calibration (PROG Mode)

Community Findings

Input Voltage Calibration:

  1. Read input voltage with the L command.
  2. Compare against an external voltmeter; should agree within 5 V.
  3. Enter PROG mode: send 1, wait 4 seconds, send 1 again. UPS responds PROG.
  4. Use + / - to adjust the reported value to match the external meter.
  5. Press R to save the corrected value to EEPROM.

Output Voltage (O command):

  • Cannot be fine-tuned via PROG mode.
  • If the reading is off by more than 5 V from external measurement, suspect a hardware fault.

Load Power (P command):

  • Verify against an external wattmeter.
  • For SU700, 100% load equals approximately 400 W.

Battery Voltage (B command):

  • Should match a DC voltmeter across the battery terminals.
  • Set the B value 1--2 tenths of a volt higher than the voltmeter reading to prevent overcharging.

Application Support

Capability Status Detail
Read input voltage (L command) Supported Fast-polled every ~2 s.
Read output voltage (O command) Supported Fast-polled every ~2 s.
Read load power (P command) Supported Fast-polled every ~2 s. Load watts computed from model rating via MODEL_WATTAGE table.
Read battery voltage (B command) Supported Fast-polled every ~2 s.
PROG mode entry (1 ... 4 s ... 1) Supported Service tab: Enter PROG button with confirmation dialog.
PROG mode +/- adjustment Supported Service tab: +/- buttons adjust value in real-time.
PROG mode R save to EEPROM Supported Service tab: Save (R) button with confirmation. Context-separated from standard R command.
Nominal wattage lookup per model Supported MODEL_WATTAGE dictionary in ups_manager.py covers models from 250 through 3000.

Potential Enhancements

  • Consider adding a dedicated "Service / Calibration" panel that implements the PROG mode protocol sequence. This would need:
    • The 1-wait-1 handshake with a 4-second timer.
    • +/- adjustment commands with live readback.
    • R to save, with clear warnings about EEPROM writes.
    • Strong UI guards (confirmation dialogs, danger labels) since incorrect calibration can cause overcharging or incorrect transfer behavior.
  • Add a voltage comparison helper that lets the user enter their external meter reading and shows the delta.

3. Runtime Calibration

Community Findings

  • Battery must be at 100% charge. Ideally calibrate the day after installing fresh batteries so the battery has time to fully charge.
  • Before calibrating, set item 0 (battery constant / runtime constant) to its default value.
  • Send the D command to start. The UPS discharges under load until battery voltage drops to approximately 22 V (for 24 V nominal systems).
  • Battery constants (smart constant items 4, 5, 6) are model-specific discharge curve parameters. These are not in the official UPS-Link specification.
  • Reference runtimes for SU700 at 150 W load:
    • 12 V 7 Ah batteries: 20--25 minutes.
    • 12 V 9 Ah batteries: 30--35 minutes.

Application Support

Capability Status Detail
Runtime calibration start/abort (D command) Supported Full state machine in CalibrationManager (IDLE -> CHECKING -> RUNNING -> COMPLETED/ABORTED/FAILED).
100% battery check before start Supported can_start() enforces battery_pct >= 100.0.
Calibration progress tracking Supported progress_pct computes estimated progress as battery drains from 100% to ~25%.
Calibration abort Supported Sends D again to abort; transitions to ABORTED state.
Read battery constant 0 Supported Command 0 added to registry. Displayed in Smart Constants panel and Service tab.
Set battery constant 0 to default Not supported No write path for this undocumented constant (would require PROG mode per-value targeting).
Read smart constants 4, 5, 6 Supported Commands 4, 5, 6 added to registry. Displayed in Smart Constants panel and Service tab.
Write smart constants 4, 5, 6 Not supported These are undocumented, model-specific parameters.
Runtime remaining display Supported Command j is slow-polled; shown as runtime_remaining in minutes.

Potential Enhancements

  • Add commands 0, 4, 5, 6 to the command registry as read-only "smart constants" so users can inspect them.
  • Add a pre-calibration checklist in the UI: verify 100% charge, display current battery constant 0, and warn if it has been modified from the default.
  • Provide model-specific reference runtime tables so users can compare their calibration result against expected values.

4. PROG Mode Details

Community Findings

PROG mode is a service/calibration mode that is not part of the standard UPS-Link protocol specification. It is entered by:

  1. Sending 1 (ASCII 0x31).
  2. Waiting exactly 4 seconds.
  3. Sending 1 again.
  4. UPS responds with PROG.

Once in PROG mode:

  • + and - adjust the value of the currently selected parameter.
  • R saves the changed value to EEPROM (different from the standard R = "return to simple mode" behavior).
  • This mode allows calibration of voltage readings and other internal parameters that cannot be changed through the normal Edit (-) cycling mechanism.

Application Support

Capability Status Detail
PROG mode entry Supported Service tab with confirmation dialog.
PROG mode value adjustment Supported +/- buttons in Service tab.
PROG mode EEPROM save Supported Save (R) button with confirmation in Service tab.
Standard Edit cycling for EEPROM settings Supported Full implementation with count_edits_needed(), verification read-back, and all 12 editable settings.
EEPROM factory reset (z command) Supported Sends z, expects CLEAR, then re-reads all settings.

Potential Enhancements

  • If PROG mode support is added, it must be clearly separated from the standard Edit workflow. The command character R has a different meaning in each context.
  • Consider a "service mode" feature gate that must be explicitly enabled, since PROG mode changes can affect UPS safety behavior.

5. Smart Constants (Undocumented Commands)

Community Findings

Command Description Notes
0 Battery discharge curve / runtime constant Should be reset to default before runtime calibration.
4 Battery discharge curve constant (low) Model-specific.
5 Battery discharge curve constant (mid) Model-specific.
6 Battery discharge curve constant (high) Model-specific.

These commands are confirmed to work across multiple Smart-UPS models. They are used internally by the UPS firmware to compute runtime estimates from the battery discharge curve. All other standard commands documented in the UPS-Link spec match our implementation.

Application Support

Capability Status Detail
Standard command set (Y, A, K, S, U, W, Z, etc.) Supported All documented UPS-Link commands are in COMMANDS registry.
Inquiry commands (B, C, F, L, M, N, O, P, Q, etc.) Supported Full coverage with fast/slow polling and one-time reads.
Editable settings (E, c, x, u, l, e, o, s, q, k, p, r) Supported 12 editable settings with cycle-edit and direct-edit modes.
Smart constant 0 Supported Read-only, displayed in UI.
Smart constants 4, 5, 6 Supported Read-only, displayed in UI.

Potential Enhancements

  • Add 0, 4, 5, 6 as read-only commands in the COMMANDS dict with response_format="numeric".
  • Display them in a "Smart Constants" section of the UI, clearly labeled as undocumented / model-specific.
  • Do not make them editable through the standard Edit path unless PROG mode is fully implemented and tested.

6. Hardware Repair Notes

Community Findings

Common failure modes on Smart-UPS boards (not applicable to software, but important context for field service):

Component Failure Mode Replacement Part
Electrolytic capacitors (22 uF / 16 V) Dry out, causing driver circuit failure Replace all electrolytics preventively
Power FETs (IRFZ46, IRFP50N06) Destruction (often caused by dried caps) Direct replacement
Small-signal transistors (2N2222 / 2N2907) Fail in driver pairs Replace in matched pairs
MOSFET drivers (2N7000) Fail alongside power FETs Direct replacement
Logic ICs (4010, 74C14) Damaged by overcurrent events Direct replacement
Faston connectors Corrosion, loose fit Inspect and re-crimp
Transformer connector Oxidation, poor contact Clean or replace
Relays Welded contacts, coil failure Direct replacement
CPU socket Poor contact from thermal cycling Re-seat or replace socket

Application Support

Capability Status Detail
Fault register decoding (Q, ~, ', 8) Supported Status, State, Trip1, and Trip registers are read and decoded. Can help identify whether a hardware fault is present.
Transfer cause logging (G command) Supported Captures reason for last transfer (R/H/L/T/O/S).
Self-test / battery test (W command) Supported Can identify battery or circuit failures.
Board-level hardware diagnosis Outside scope Software cannot diagnose individual component failures. This requires bench testing with a multimeter and oscilloscope.

Practical Notes

  • If a UPS consistently fails self-tests (X returns NG) after battery replacement, suspect board-level component failure -- particularly dried electrolytics.
  • If transfer cause (G) repeatedly shows unexpected values, check relay contacts and FET health.
  • Our app can serve as a diagnostic aid by monitoring registers and test results over time, but it cannot replace hands-on hardware inspection.

Summary: Coverage Matrix

Topic Fully Supported Partially Supported Not Supported / Out of Scope
Temperature monitoring Read temp (C), threshold alert, session history -- Persistent log across sessions
Battery age tracking Battery replace date (x), proactive age warning -- --
Input voltage reading L command, fast poll, PROG mode calibration -- --
Output voltage reading O command, fast poll, PROG mode calibration -- --
Battery voltage reading B command, fast poll, PROG mode calibration -- --
Load power reading P command + wattage calc -- --
Runtime calibration D command, full state machine, pre-check with constant 0 -- Resetting constant 0 to default
Editable EEPROM settings 13 settings (incl. battery packs), cycle + direct edit -- --
EEPROM factory reset z command -- --
PROG mode Full: enter, +/- adjust, save, exit -- --
Smart constants (0, 4, 5, 6) Read-only display in UI and Service tab -- Write/edit (requires PROG mode per value)
Voltage comparison Compare UPS vs external meter, show delta -- --
Fault register decoding Q, ~, ', 8 registers -- --
Hardware board repair -- Fault registers aid diagnosis Board-level repair is outside scope

Implementation Status

All items from the original "Recommended Priority" list have been implemented:

  1. DONE -- Smart constants (read-only): Commands 0, 4, 5, 6 added to command registry and polled at connect time. Displayed in Smart Constants panel (main tab) and Service tab calibration pre-check section.

  2. DONE -- Temperature alerting: Configurable threshold (default 40 C) in Service tab. Red warning banner appears in main tab when temperature exceeds threshold. Alert messages logged.

  3. DONE -- Calibration pre-checks: Battery constant 0 displayed in Service tab before calibration. Warning shown if constant differs from default. Battery percentage check displayed.

  4. DONE -- Temperature logging: Session-based history (up to 360 readings). Min/max/average summary displayed in Service tab. History resets on disconnect.

  5. DONE -- PROG mode support: Full implementation in Service tab with enter, +/- adjust, read, save (R), and exit. Confirmation dialogs and warning banners protect against accidental changes.

  6. DONE -- Voltage comparison tool: Dialog in main tab (Compare Voltages button) lets user enter external meter readings for input, output, and battery voltage. Shows UPS vs meter delta.

  7. DONE -- Battery packs editing: Number of external battery packs (> command) added as editable CAUTION-tier setting. Affects runtime calculation.

  8. DONE -- Battery age warning: Battery age computed from battery_replace_date. Yellow warning banner in main tab when batteries exceed 2 years.