| Condition | Internal Temp | Expected Battery Life |
|---|---|---|
| Open desk, 25 C room | 34--36 C | ~6 years |
| Open desk, 35 C ambient (or enclosed cabinet) | ~45 C | ~1.5 years |
| Enclosed cabinet in summer | >50 C | <1 year |
Key observations:
- Battery life halves for every 10 C increase above 25 C.
- At 45 C and above, battery brand is irrelevant --- all fail within two years.
- An 80x80x40 mm Sunon fan (15--20 W) reduced idle temperature from 34--36 C down to 24--26 C, and limited battery-discharge temperature rise to 2 C (versus 46 C without cooling).
- Fan should be powered from UPS input (mains side), not the UPS output, to avoid draining the battery during an outage.
| Capability | Status | Detail |
|---|---|---|
| Read internal temperature (C command) | Supported | Polled every ~10 s (slow poll). Displayed in the UI as temperature. |
| Temperature trend / logging | Supported | Session-based history (up to 360 readings, ~1 hour at 10s intervals). Min/max/average summary shown in Service tab. |
| High-temperature alert | Supported | Configurable threshold (default 40 C) in Service tab. Red warning banner in main tab when exceeded. Alert logged to status messages. |
| Battery age tracking | Supported | The battery_replace_date (x command) is editable. Users can record the date batteries were last replaced. |
- Add a configurable high-temperature warning threshold (e.g., alert if C > 40 C).
- Add persistent temperature logging so users can identify enclosure heat problems before batteries are damaged.
- Surface a "battery age" indicator computed from
battery_replace_dateand the temperature history, so users get a proactive replacement reminder.
Input Voltage Calibration:
- Read input voltage with the L command.
- Compare against an external voltmeter; should agree within 5 V.
- Enter PROG mode: send
1, wait 4 seconds, send1again. UPS respondsPROG. - Use
+/-to adjust the reported value to match the external meter. - Press
Rto save the corrected value to EEPROM.
Output Voltage (O command):
- Cannot be fine-tuned via PROG mode.
- If the reading is off by more than 5 V from external measurement, suspect a hardware fault.
Load Power (P command):
- Verify against an external wattmeter.
- For SU700, 100% load equals approximately 400 W.
Battery Voltage (B command):
- Should match a DC voltmeter across the battery terminals.
- Set the B value 1--2 tenths of a volt higher than the voltmeter reading to prevent overcharging.
| Capability | Status | Detail |
|---|---|---|
| Read input voltage (L command) | Supported | Fast-polled every ~2 s. |
| Read output voltage (O command) | Supported | Fast-polled every ~2 s. |
| Read load power (P command) | Supported | Fast-polled every ~2 s. Load watts computed from model rating via MODEL_WATTAGE table. |
| Read battery voltage (B command) | Supported | Fast-polled every ~2 s. |
PROG mode entry (1 ... 4 s ... 1) |
Supported | Service tab: Enter PROG button with confirmation dialog. |
PROG mode +/- adjustment |
Supported | Service tab: +/- buttons adjust value in real-time. |
PROG mode R save to EEPROM |
Supported | Service tab: Save (R) button with confirmation. Context-separated from standard R command. |
| Nominal wattage lookup per model | Supported | MODEL_WATTAGE dictionary in ups_manager.py covers models from 250 through 3000. |
- Consider adding a dedicated "Service / Calibration" panel that implements the
PROG mode protocol sequence. This would need:
- The
1-wait-1handshake with a 4-second timer. +/-adjustment commands with live readback.Rto save, with clear warnings about EEPROM writes.- Strong UI guards (confirmation dialogs, danger labels) since incorrect calibration can cause overcharging or incorrect transfer behavior.
- The
- Add a voltage comparison helper that lets the user enter their external meter reading and shows the delta.
- Battery must be at 100% charge. Ideally calibrate the day after installing fresh batteries so the battery has time to fully charge.
- Before calibrating, set item
0(battery constant / runtime constant) to its default value. - Send the
Dcommand to start. The UPS discharges under load until battery voltage drops to approximately 22 V (for 24 V nominal systems). - Battery constants (smart constant items
4,5,6) are model-specific discharge curve parameters. These are not in the official UPS-Link specification. - Reference runtimes for SU700 at 150 W load:
- 12 V 7 Ah batteries: 20--25 minutes.
- 12 V 9 Ah batteries: 30--35 minutes.
| Capability | Status | Detail |
|---|---|---|
| Runtime calibration start/abort (D command) | Supported | Full state machine in CalibrationManager (IDLE -> CHECKING -> RUNNING -> COMPLETED/ABORTED/FAILED). |
| 100% battery check before start | Supported | can_start() enforces battery_pct >= 100.0. |
| Calibration progress tracking | Supported | progress_pct computes estimated progress as battery drains from 100% to ~25%. |
| Calibration abort | Supported | Sends D again to abort; transitions to ABORTED state. |
Read battery constant 0 |
Supported | Command 0 added to registry. Displayed in Smart Constants panel and Service tab. |
Set battery constant 0 to default |
Not supported | No write path for this undocumented constant (would require PROG mode per-value targeting). |
Read smart constants 4, 5, 6 |
Supported | Commands 4, 5, 6 added to registry. Displayed in Smart Constants panel and Service tab. |
Write smart constants 4, 5, 6 |
Not supported | These are undocumented, model-specific parameters. |
| Runtime remaining display | Supported | Command j is slow-polled; shown as runtime_remaining in minutes. |
- Add commands
0,4,5,6to the command registry as read-only "smart constants" so users can inspect them. - Add a pre-calibration checklist in the UI: verify 100% charge, display current
battery constant
0, and warn if it has been modified from the default. - Provide model-specific reference runtime tables so users can compare their calibration result against expected values.
PROG mode is a service/calibration mode that is not part of the standard UPS-Link protocol specification. It is entered by:
- Sending
1(ASCII 0x31). - Waiting exactly 4 seconds.
- Sending
1again. - UPS responds with
PROG.
Once in PROG mode:
+and-adjust the value of the currently selected parameter.Rsaves the changed value to EEPROM (different from the standardR= "return to simple mode" behavior).- This mode allows calibration of voltage readings and other internal parameters
that cannot be changed through the normal Edit (
-) cycling mechanism.
| Capability | Status | Detail |
|---|---|---|
| PROG mode entry | Supported | Service tab with confirmation dialog. |
| PROG mode value adjustment | Supported | +/- buttons in Service tab. |
| PROG mode EEPROM save | Supported | Save (R) button with confirmation in Service tab. |
| Standard Edit cycling for EEPROM settings | Supported | Full implementation with count_edits_needed(), verification read-back, and all 12 editable settings. |
| EEPROM factory reset (z command) | Supported | Sends z, expects CLEAR, then re-reads all settings. |
- If PROG mode support is added, it must be clearly separated from the standard
Edit workflow. The command character
Rhas a different meaning in each context. - Consider a "service mode" feature gate that must be explicitly enabled, since PROG mode changes can affect UPS safety behavior.
| Command | Description | Notes |
|---|---|---|
0 |
Battery discharge curve / runtime constant | Should be reset to default before runtime calibration. |
4 |
Battery discharge curve constant (low) | Model-specific. |
5 |
Battery discharge curve constant (mid) | Model-specific. |
6 |
Battery discharge curve constant (high) | Model-specific. |
These commands are confirmed to work across multiple Smart-UPS models. They are used internally by the UPS firmware to compute runtime estimates from the battery discharge curve. All other standard commands documented in the UPS-Link spec match our implementation.
| Capability | Status | Detail |
|---|---|---|
| Standard command set (Y, A, K, S, U, W, Z, etc.) | Supported | All documented UPS-Link commands are in COMMANDS registry. |
| Inquiry commands (B, C, F, L, M, N, O, P, Q, etc.) | Supported | Full coverage with fast/slow polling and one-time reads. |
| Editable settings (E, c, x, u, l, e, o, s, q, k, p, r) | Supported | 12 editable settings with cycle-edit and direct-edit modes. |
Smart constant 0 |
Supported | Read-only, displayed in UI. |
Smart constants 4, 5, 6 |
Supported | Read-only, displayed in UI. |
- Add
0,4,5,6as read-only commands in theCOMMANDSdict withresponse_format="numeric". - Display them in a "Smart Constants" section of the UI, clearly labeled as undocumented / model-specific.
- Do not make them editable through the standard Edit path unless PROG mode is fully implemented and tested.
Common failure modes on Smart-UPS boards (not applicable to software, but important context for field service):
| Component | Failure Mode | Replacement Part |
|---|---|---|
| Electrolytic capacitors (22 uF / 16 V) | Dry out, causing driver circuit failure | Replace all electrolytics preventively |
| Power FETs (IRFZ46, IRFP50N06) | Destruction (often caused by dried caps) | Direct replacement |
| Small-signal transistors (2N2222 / 2N2907) | Fail in driver pairs | Replace in matched pairs |
| MOSFET drivers (2N7000) | Fail alongside power FETs | Direct replacement |
| Logic ICs (4010, 74C14) | Damaged by overcurrent events | Direct replacement |
| Faston connectors | Corrosion, loose fit | Inspect and re-crimp |
| Transformer connector | Oxidation, poor contact | Clean or replace |
| Relays | Welded contacts, coil failure | Direct replacement |
| CPU socket | Poor contact from thermal cycling | Re-seat or replace socket |
| Capability | Status | Detail |
|---|---|---|
| Fault register decoding (Q, ~, ', 8) | Supported | Status, State, Trip1, and Trip registers are read and decoded. Can help identify whether a hardware fault is present. |
| Transfer cause logging (G command) | Supported | Captures reason for last transfer (R/H/L/T/O/S). |
| Self-test / battery test (W command) | Supported | Can identify battery or circuit failures. |
| Board-level hardware diagnosis | Outside scope | Software cannot diagnose individual component failures. This requires bench testing with a multimeter and oscilloscope. |
- If a UPS consistently fails self-tests (X returns NG) after battery replacement, suspect board-level component failure -- particularly dried electrolytics.
- If transfer cause (G) repeatedly shows unexpected values, check relay contacts and FET health.
- Our app can serve as a diagnostic aid by monitoring registers and test results over time, but it cannot replace hands-on hardware inspection.
| Topic | Fully Supported | Partially Supported | Not Supported / Out of Scope |
|---|---|---|---|
| Temperature monitoring | Read temp (C), threshold alert, session history | -- | Persistent log across sessions |
| Battery age tracking | Battery replace date (x), proactive age warning | -- | -- |
| Input voltage reading | L command, fast poll, PROG mode calibration | -- | -- |
| Output voltage reading | O command, fast poll, PROG mode calibration | -- | -- |
| Battery voltage reading | B command, fast poll, PROG mode calibration | -- | -- |
| Load power reading | P command + wattage calc | -- | -- |
| Runtime calibration | D command, full state machine, pre-check with constant 0 | -- | Resetting constant 0 to default |
| Editable EEPROM settings | 13 settings (incl. battery packs), cycle + direct edit | -- | -- |
| EEPROM factory reset | z command | -- | -- |
| PROG mode | Full: enter, +/- adjust, save, exit | -- | -- |
| Smart constants (0, 4, 5, 6) | Read-only display in UI and Service tab | -- | Write/edit (requires PROG mode per value) |
| Voltage comparison | Compare UPS vs external meter, show delta | -- | -- |
| Fault register decoding | Q, ~, ', 8 registers | -- | -- |
| Hardware board repair | -- | Fault registers aid diagnosis | Board-level repair is outside scope |
All items from the original "Recommended Priority" list have been implemented:
-
DONE -- Smart constants (read-only): Commands
0,4,5,6added to command registry and polled at connect time. Displayed in Smart Constants panel (main tab) and Service tab calibration pre-check section. -
DONE -- Temperature alerting: Configurable threshold (default 40 C) in Service tab. Red warning banner appears in main tab when temperature exceeds threshold. Alert messages logged.
-
DONE -- Calibration pre-checks: Battery constant
0displayed in Service tab before calibration. Warning shown if constant differs from default. Battery percentage check displayed. -
DONE -- Temperature logging: Session-based history (up to 360 readings). Min/max/average summary displayed in Service tab. History resets on disconnect.
-
DONE -- PROG mode support: Full implementation in Service tab with enter, +/- adjust, read, save (R), and exit. Confirmation dialogs and warning banners protect against accidental changes.
-
DONE -- Voltage comparison tool: Dialog in main tab (Compare Voltages button) lets user enter external meter readings for input, output, and battery voltage. Shows UPS vs meter delta.
-
DONE -- Battery packs editing: Number of external battery packs (> command) added as editable CAUTION-tier setting. Affects runtime calculation.
-
DONE -- Battery age warning: Battery age computed from
battery_replace_date. Yellow warning banner in main tab when batteries exceed 2 years.