diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/.modelkit-config b/commercial measures/SWHC005-05 Water Cooled Chiller/.modelkit-config new file mode 100644 index 00000000..b11027e5 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/.modelkit-config @@ -0,0 +1,24 @@ + +# Paths are expanded relative to this modelkit-config file. + +prototypes-dir = '../../prototypes' +templates-dir = '../../templates/energyplus/templates' +weather-dir = '../../weather' +codes-dir = '../../codes' + +max-workers = 12 # Maximum number of simulations to run in parallel + + +[template-compose] +annotate = true +indent = " " +esc-line = "! " +dirs = '~\Documents\Modelkit Caboodle\templates\energyplus\templates' # Must be an absolute path + +[energyplus-run] +engine = 'C:\EnergyPlusV22-2-0' # Must be an absolute path +#engine = '/Applications/EnergyPlus-22-2-0' # Must be an absolute path +#engine = '/Applications/EnergyPlus-9-2-0' # Must be an absolute path +readvars = true +keep = false +output-files = "eplusout.err; eplusout.sql; eplustbl.htm; eplusvar.csv" diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/DEER_EnergyPlus_Modelkit_Measure_list_working.xlsx b/commercial measures/SWHC005-05 Water Cooled Chiller/DEER_EnergyPlus_Modelkit_Measure_list_working.xlsx new file mode 100644 index 00000000..fe185382 Binary files /dev/null and b/commercial measures/SWHC005-05 Water Cooled Chiller/DEER_EnergyPlus_Modelkit_Measure_list_working.xlsx differ diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/ECC&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/ECC&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/ECC&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/ESe&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/ESe&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/ESe&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/EUn&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/EUn&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/EUn&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/Hsp&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/Hsp&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/Hsp&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/MBT&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/MBT&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/MBT&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/Nrs&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/Nrs&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/Nrs&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/OfL&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/OfL&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/OfL&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/OfS&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/OfS&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/OfS&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/Rt3&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/Rt3&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cases/Rt3&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/climates.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/climates.csv new file mode 100644 index 00000000..2b7ad0aa --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/climates.csv @@ -0,0 +1,17 @@ +skip,climate,weather_file,climate_zone,codes_file +,CZ01,CA_EUREKA_725940S_CZ2022.epw,1,T24_weight_averaged_ex.csv +,CZ02,CA_NAPA-CO_724955S_CZ2022.epw,2,T24_weight_averaged_ex.csv +,CZ03,CA_OAKLAND-METRO-AP_724930S_CZ2022.epw,3,T24_weight_averaged_ex.csv +,CZ04,CA_SAN-JOSE-IAP_724945S_CZ2022.epw,4,T24_weight_averaged_ex.csv +,CZ05,CA_SANTA-MARIA-PUBLIC-AP_723940S_CZ2022.epw,5,T24_weight_averaged_ex.csv +,CZ06,CA_LOS-ANGELES-IAP_722950S_CZ2022.epw,6,T24_weight_averaged_ex.csv +,CZ07,CA_SAN-DIEGO-LINDBERGH-FLD_722900S_CZ2022.epw,7,T24_weight_averaged_ex.csv +,CZ08,CA_LONG-BEACH-DAUGHERTY-FLD_722970S_CZ2022.epw,8,T24_weight_averaged_ex.csv +,CZ09,CA_LOS-ANGELES-DOWNTOWN-USC_722874S_CZ2022.epw,9,T24_weight_averaged_ex.csv +,CZ10,CA_RIVERSIDE-MUNI_722869S_CZ2022.epw,10,T24_weight_averaged_ex.csv +,CZ11,CA_RED-BLUFF-MUNI-AP_725910S_CZ2022.epw,11,T24_weight_averaged_ex.csv +,CZ12,CA_STOCKTON-METRO-AP_724920S_CZ2022.epw,12,T24_weight_averaged_ex.csv +,CZ13,CA_FRESNO-YOSEMITE-IAP_723890S_CZ2022.epw,13,T24_weight_averaged_ex.csv +,CZ14,CA_DAGGETT-BARSTOW-AP_723815S_CZ2022.epw,14,T24_weight_averaged_ex.csv +,CZ15,CA_EL-CENTRO-NAF_722810S_CZ2022.epw,15,T24_weight_averaged_ex.csv +,CZ16,CA_BISHOP-AP_724800S_CZ2022.epw,16,T24_weight_averaged_ex.csv diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cohorts.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cohorts.csv new file mode 100644 index 00000000..2f3a89a0 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/cohorts.csv @@ -0,0 +1,27 @@ +skip,cohort,root,wall_type,:wall_base_cavity_insul,:wall_base_cont_insul,:roof_base_cont_insul,:window_u,:window_shgc,:window_transmittance,:floor_base_cont_insul,:office_large_light_area,:kitchen_light_area,:dining_fast_light_area,:classroom_class_light_area,:corridor_light_area,:retail_sales_light_area,:storage_warehouse_light_area,:computer_light_area,:lobby_light_area,:guestroom_light_area,:auditorium_light_area,:conference_light_area,:dining_fine_light_area,:gym_light_area,:restroom_light_area,:health_patient_light_area,:industrial_low_light_area,:laundry_light_area,:auto_light_area,:classroom_shop_light_area,:grocery_light_area,:health_operating_light_area,:industrial_high_light_area,:lab_light_area,:mech_light_area,:office_open_light_area,:storage_refrig_light_area,:office_small_light_area,:main_oa_econ_max_temp +,Asm&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Asm/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""auditorium"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,ECC&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,ECC/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""computer"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""classroom_shop"", ""LPD"")['W/ft2']",,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,EPr&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,EPr/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,"%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""gym"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,ERC&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,ERC/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,"%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,ESe&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,ESe/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,"%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""computer"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""gym"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,EUn&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,EUn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""computer"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""guestroom"", ""LPD"")['W/ft2']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""industrial_low"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Fin&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Fin/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Gro&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Gro/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""grocery"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""industrial_high"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""storage_refrig"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Hsp&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Hsp/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']",,,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""health_patient"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""health_operating"", ""LPD"")['W/ft2']",,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Htl&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Htl/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""lobby"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""guestroom"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""dining_fine"", ""LPD"")['W/ft2']",,,,,"%= codes.lookup(""Lighting Power Density"", ""laundry"", ""LPD"")['W/ft2']",,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Lib&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Lib/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""conference"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,MBT&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,MBT/templates/root.pxt,Metal Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""computer"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""conference"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""lab"", ""LPD"")['W/ft2']",,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,MLI&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,MLI/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""industrial_low"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Mtl&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Mtl/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,,,"%= codes.lookup(""Lighting Power Density"", ""guestroom"", ""LPD"")['W/ft2']",,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""laundry"", ""LPD"")['W/ft2']",,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Nrs&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Nrs/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""health_patient"", ""LPD"")['W/ft2']",,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,OfL&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,OfL/templates/root.pxt,Metal Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""lobby"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""mech"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""office_open"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,OfS&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,OfS/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""office_small"", ""LPD"")['W/ft2']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Rel&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Rel/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""auditorium"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,RFF&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,RFF/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,"%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""lobby"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""restroom"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,RSD&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,RSD/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,"%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""lobby"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""dining_fine"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""restroom"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Rt3&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Rt3/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,RtL&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,RtL/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""auto"", ""LPD"")['W/ft2']",,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,RtS&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,RtS/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,SCn&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,SCn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,SUn&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,SUn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Wrf&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,WRf/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/query.txt b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/query.txt new file mode 100644 index 00000000..66e76be7 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Ex/query.txt @@ -0,0 +1,30 @@ +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Energy Per Total Building Area/Net Site Energy, Net Site EUI +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Total Energy/Net Site Energy, Net Site Energy +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Total End Uses, Electricity +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Total End Uses, Natural Gas + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Energy Per Total Building Area/Net Source Energy, Net Source EUI +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Total Energy/Net Source Energy, Net Source Energy + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Total End Uses, Total +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heating, Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Cooling, Cooling +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Interior Lighting, Interior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Exterior Lighting, Exterior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Interior Equipment, Interior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Exterior Equipment, Exterior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Fans, Fans +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Pumps, Pumps +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heat Rejection, Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Humidification, Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heat Recovery, Heat Recovery +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Water Systems, Water Systems +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Refrigeration, Refrigeration +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Generators, Generators + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Heat Rejection, Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Humidification, Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Water Systems, Water Systems + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Comfort and Setpoint Not Met Summary/Facility/Time Setpoint Not Met During Occupied Heating, Unmet Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Comfort and Setpoint Not Met Summary/Facility/Time Setpoint Not Met During Occupied Cooling, Unmet Cooling diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/cases/Htl&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/cases/Htl&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/cases/Htl&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/climates.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/climates.csv new file mode 100644 index 00000000..9f5cc7a8 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/climates.csv @@ -0,0 +1,17 @@ +skip,climate,weather_file,climate_zone,codes_file +,CZ01,CA_EUREKA_725940S_CZ2022.epw,1,T24_weight_averaged_ex_Htl.csv +,CZ02,CA_NAPA-CO_724955S_CZ2022.epw,2,T24_weight_averaged_ex_Htl.csv +,CZ03,CA_OAKLAND-METRO-AP_724930S_CZ2022.epw,3,T24_weight_averaged_ex_Htl.csv +,CZ04,CA_SAN-JOSE-IAP_724945S_CZ2022.epw,4,T24_weight_averaged_ex_Htl.csv +,CZ05,CA_SANTA-MARIA-PUBLIC-AP_723940S_CZ2022.epw,5,T24_weight_averaged_ex_Htl.csv +,CZ06,CA_LOS-ANGELES-IAP_722950S_CZ2022.epw,6,T24_weight_averaged_ex_Htl.csv +,CZ07,CA_SAN-DIEGO-LINDBERGH-FLD_722900S_CZ2022.epw,7,T24_weight_averaged_ex_Htl.csv +,CZ08,CA_LONG-BEACH-DAUGHERTY-FLD_722970S_CZ2022.epw,8,T24_weight_averaged_ex_Htl.csv +,CZ09,CA_LOS-ANGELES-DOWNTOWN-USC_722874S_CZ2022.epw,9,T24_weight_averaged_ex_Htl.csv +,CZ10,CA_RIVERSIDE-MUNI_722869S_CZ2022.epw,10,T24_weight_averaged_ex_Htl.csv +,CZ11,CA_RED-BLUFF-MUNI-AP_725910S_CZ2022.epw,11,T24_weight_averaged_ex_Htl.csv +,CZ12,CA_STOCKTON-METRO-AP_724920S_CZ2022.epw,12,T24_weight_averaged_ex_Htl.csv +,CZ13,CA_FRESNO-YOSEMITE-IAP_723890S_CZ2022.epw,13,T24_weight_averaged_ex_Htl.csv +,CZ14,CA_DAGGETT-BARSTOW-AP_723815S_CZ2022.epw,14,T24_weight_averaged_ex_Htl.csv +,CZ15,CA_EL-CENTRO-NAF_722810S_CZ2022.epw,15,T24_weight_averaged_ex_Htl.csv +,CZ16,CA_BISHOP-AP_724800S_CZ2022.epw,16,T24_weight_averaged_ex_Htl.csv diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/cohorts.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/cohorts.csv new file mode 100644 index 00000000..d0195daa --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/cohorts.csv @@ -0,0 +1,26 @@ +skip,cohort,root,wall_type,:wall_base_cavity_insul,:wall_base_cont_insul,:roof_base_cont_insul,:window_u,:window_shgc,:window_transmittance,:floor_base_cont_insul,:main_oa_econ_max_temp +#,Asm,Asm/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,ECC,ECC/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,EPr,EPr/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,ERC,ERC/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,ESe,ESe/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,EUn,EUn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Fin,Fin/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Gro,Gro/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Hsp,Hsp/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Htl&0&cAVVG&Ex&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Htl/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Lib,Lib/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,MBT,MBT/templates/root.pxt,Metal Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,MLI,MLI/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Mtl,Mtl/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Nrs,Nrs/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,OfL,OfL/templates/root.pxt,Metal Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,OfS,OfS/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Rel,Rel/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RFF,RFF/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RSD,RSD/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Rt3,Rt3/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RtL,RtL/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RtS,RtS/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,SCn,SCn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,SUn,SUn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/query.txt b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/query.txt new file mode 100644 index 00000000..66e76be7 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_Ex/query.txt @@ -0,0 +1,30 @@ +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Energy Per Total Building Area/Net Site Energy, Net Site EUI +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Total Energy/Net Site Energy, Net Site Energy +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Total End Uses, Electricity +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Total End Uses, Natural Gas + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Energy Per Total Building Area/Net Source Energy, Net Source EUI +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Total Energy/Net Source Energy, Net Source Energy + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Total End Uses, Total +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heating, Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Cooling, Cooling +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Interior Lighting, Interior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Exterior Lighting, Exterior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Interior Equipment, Interior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Exterior Equipment, Exterior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Fans, Fans +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Pumps, Pumps +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heat Rejection, Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Humidification, Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heat Recovery, Heat Recovery +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Water Systems, Water Systems +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Refrigeration, Refrigeration +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Generators, Generators + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Heat Rejection, Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Humidification, Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Water Systems, Water Systems + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Comfort and Setpoint Not Met Summary/Facility/Time Setpoint Not Met During Occupied Heating, Unmet Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Comfort and Setpoint Not Met Summary/Facility/Time Setpoint Not Met During Occupied Cooling, Unmet Cooling diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/cases/Htl&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/cases/Htl&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/cases/Htl&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/climates.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/climates.csv new file mode 100644 index 00000000..14f1e59a --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/climates.csv @@ -0,0 +1,17 @@ +skip,climate,weather_file,climate_zone,codes_file +,CZ01,CA_EUREKA_725940S_CZ2022.epw,1,T24_2025_new_Htl.csv +,CZ02,CA_NAPA-CO_724955S_CZ2022.epw,2,T24_2025_new_Htl.csv +,CZ03,CA_OAKLAND-METRO-AP_724930S_CZ2022.epw,3,T24_2025_new_Htl.csv +,CZ04,CA_SAN-JOSE-IAP_724945S_CZ2022.epw,4,T24_2025_new_Htl.csv +,CZ05,CA_SANTA-MARIA-PUBLIC-AP_723940S_CZ2022.epw,5,T24_2025_new_Htl.csv +,CZ06,CA_LOS-ANGELES-IAP_722950S_CZ2022.epw,6,T24_2025_new_Htl.csv +,CZ07,CA_SAN-DIEGO-LINDBERGH-FLD_722900S_CZ2022.epw,7,T24_2025_new_Htl.csv +,CZ08,CA_LONG-BEACH-DAUGHERTY-FLD_722970S_CZ2022.epw,8,T24_2025_new_Htl.csv +,CZ09,CA_LOS-ANGELES-DOWNTOWN-USC_722874S_CZ2022.epw,9,T24_2025_new_Htl.csv +,CZ10,CA_RIVERSIDE-MUNI_722869S_CZ2022.epw,10,T24_2025_new_Htl.csv +,CZ11,CA_RED-BLUFF-MUNI-AP_725910S_CZ2022.epw,11,T24_2025_new_Htl.csv +,CZ12,CA_STOCKTON-METRO-AP_724920S_CZ2022.epw,12,T24_2025_new_Htl.csv +,CZ13,CA_FRESNO-YOSEMITE-IAP_723890S_CZ2022.epw,13,T24_2025_new_Htl.csv +,CZ14,CA_DAGGETT-BARSTOW-AP_723815S_CZ2022.epw,14,T24_2025_new_Htl.csv +,CZ15,CA_EL-CENTRO-NAF_722810S_CZ2022.epw,15,T24_2025_new_Htl.csv +,CZ16,CA_BISHOP-AP_724800S_CZ2022.epw,16,T24_2025_new_Htl.csv diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/cohorts.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/cohorts.csv new file mode 100644 index 00000000..c1644d09 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/cohorts.csv @@ -0,0 +1,26 @@ +skip,cohort,root,wall_type,:wall_base_cavity_insul,:wall_base_cont_insul,:roof_base_cont_insul,:window_u,:window_shgc,:window_transmittance,:floor_base_cont_insul,:main_oa_econ_max_temp +#,Asm,Asm/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,ECC,ECC/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,EPr,EPr/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,ERC,ERC/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,ESe,ESe/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,EUn,EUn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Fin,Fin/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Gro,Gro/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Hsp,Hsp/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Htl&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Htl/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Lib,Lib/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,MBT,MBT/templates/root.pxt,Metal Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,MLI,MLI/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Mtl,Mtl/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Nrs,Nrs/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,OfL,OfL/templates/root.pxt,Metal Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,OfS,OfS/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Rel,Rel/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RFF,RFF/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RSD,RSD/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Rt3,Rt3/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RtL,RtL/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RtS,RtS/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,SCn,SCn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,SUn,SUn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/query.txt b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/query.txt new file mode 100644 index 00000000..66e76be7 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_Htl_New/query.txt @@ -0,0 +1,30 @@ +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Energy Per Total Building Area/Net Site Energy, Net Site EUI +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Total Energy/Net Site Energy, Net Site Energy +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Total End Uses, Electricity +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Total End Uses, Natural Gas + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Energy Per Total Building Area/Net Source Energy, Net Source EUI +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Total Energy/Net Source Energy, Net Source Energy + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Total End Uses, Total +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heating, Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Cooling, Cooling +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Interior Lighting, Interior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Exterior Lighting, Exterior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Interior Equipment, Interior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Exterior Equipment, Exterior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Fans, Fans +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Pumps, Pumps +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heat Rejection, Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Humidification, Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heat Recovery, Heat Recovery +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Water Systems, Water Systems +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Refrigeration, Refrigeration +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Generators, Generators + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Heat Rejection, Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Humidification, Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Water Systems, Water Systems + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Comfort and Setpoint Not Met Summary/Facility/Time Setpoint Not Met During Occupied Heating, Unmet Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Comfort and Setpoint Not Met Summary/Facility/Time Setpoint Not Met During Occupied Cooling, Unmet Cooling diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/ECC&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/ECC&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/ECC&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/ESe&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/ESe&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/ESe&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/EUn&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/EUn&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/EUn&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/Hsp&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/Hsp&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/Hsp&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/MBT&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/MBT&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/MBT&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/Nrs&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/Nrs&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/Nrs&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/OfL&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/OfL&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/OfL&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/OfS&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/OfS&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..07b8d805 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/OfS&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/Rt3&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/Rt3&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv new file mode 100644 index 00000000..cb064b9e --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cases/Rt3&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr.csv @@ -0,0 +1,36 @@ +skip,case_name,:main_cool_coil_type,:chw_chiller_model,:chw_chiller_plr_curve,:chw_chiller_cop,:chw_cooling_source,:chw_chiller_type,:chw_wc_option,:chw_pump_type,:chw_chiller_condenser,:cool_sizing_factor,:main_hvac_type,:heat_sizing_factor,:hvac_config,:main_atu_reheat_coil_type,:main_atu_reheat_control,:main_fan_rise,:main_heat_coil_type,:main_dx_type,:main_sat_reset_type,:main_sat_temp_max,:main_design_peak_load,:main_oa_econ_type,:main_cool_coil_cop,:main_dx_comp_speed,:main_cool_flow_min_frac,:main_unitary_no_load_flow_method,:main_fan_speed,:main_fan_motor_eff,:main_heat_coil_cop,:main_heat_coil_eff,:main_heat_flow_frac,:hw_boiler_eff +#,defaults,WATER,WC Cent 2010 B,Bicubic,5.1,CHILLER,ELECTRIC,,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.646-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.332-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.591-kwpton-0.352-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.324-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.553-kwpton-0.343-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.415-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.315-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.544-kwpton-0.334-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.365-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.632-kwpton-0.387-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.34-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.581-kwpton-0.361-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,6.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.407-IPLV,WATER,Model 9 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.698-kwpton-0.431-IPLV,WATER,Model 7 WC Chiller,ChillerPartLoadWithLift,5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.695-kwpton-0.44-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.1,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.635-kwpton-0.4-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.595-kwpton-0.39-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.9,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldCentChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.78-kwpton-0.5-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.5,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.75-kwpton-0.49-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.7,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.68-kwpton-0.44-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.2,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.625-kwpton-0.41-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,5.6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,NE-Chiller-WtrCldScrewChlr-0.585-kwpton-0.38-IPLV,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,6,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldCentChlr-0.646-kwpton-0.365-IPLV-Base,WATER,ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Bicubic,5.4,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +,Test-WtrCldScrewChlr-0.725-kwpton-0.44-IPLV-Base,WATER,ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve,Bicubic,4.8,CHILLER,ELECTRIC,Reformulated,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Cent,WATER,WC Cent Carrier 19XR 1234kW/5.39COP/VSD,Quadratic,5.39,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 +#,Test-EIR_Screw,WATER,Screw WC Trane RTHB 1051kW/5.05COP/Valve,Quadratic,5.05,CHILLER,ELECTRIC,EIR,VARIABLE,WATERCOOLED,1.15,MZ-VAV,1.25,FLOOR,WATER,DUAL-MAX-LIMIT,5.361969['in H2O'],WATER,PNNL,WARMEST-ZONE,60.0['F'],COINCIDENT,FIXED-DRY-BULB,,,,,VARIABLE,0.9,,,0.5,0.805 diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/climates.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/climates.csv new file mode 100644 index 00000000..5b1f9662 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/climates.csv @@ -0,0 +1,17 @@ +skip,climate,weather_file,climate_zone,codes_file +,CZ01,CA_EUREKA_725940S_CZ2022.epw,1,T24_2025_new.csv +,CZ02,CA_NAPA-CO_724955S_CZ2022.epw,2,T24_2025_new.csv +,CZ03,CA_OAKLAND-METRO-AP_724930S_CZ2022.epw,3,T24_2025_new.csv +,CZ04,CA_SAN-JOSE-IAP_724945S_CZ2022.epw,4,T24_2025_new.csv +,CZ05,CA_SANTA-MARIA-PUBLIC-AP_723940S_CZ2022.epw,5,T24_2025_new.csv +,CZ06,CA_LOS-ANGELES-IAP_722950S_CZ2022.epw,6,T24_2025_new.csv +,CZ07,CA_SAN-DIEGO-LINDBERGH-FLD_722900S_CZ2022.epw,7,T24_2025_new.csv +,CZ08,CA_LONG-BEACH-DAUGHERTY-FLD_722970S_CZ2022.epw,8,T24_2025_new.csv +,CZ09,CA_LOS-ANGELES-DOWNTOWN-USC_722874S_CZ2022.epw,9,T24_2025_new.csv +,CZ10,CA_RIVERSIDE-MUNI_722869S_CZ2022.epw,10,T24_2025_new.csv +,CZ11,CA_RED-BLUFF-MUNI-AP_725910S_CZ2022.epw,11,T24_2025_new.csv +,CZ12,CA_STOCKTON-METRO-AP_724920S_CZ2022.epw,12,T24_2025_new.csv +,CZ13,CA_FRESNO-YOSEMITE-IAP_723890S_CZ2022.epw,13,T24_2025_new.csv +,CZ14,CA_DAGGETT-BARSTOW-AP_723815S_CZ2022.epw,14,T24_2025_new.csv +,CZ15,CA_EL-CENTRO-NAF_722810S_CZ2022.epw,15,T24_2025_new.csv +,CZ16,CA_BISHOP-AP_724800S_CZ2022.epw,16,T24_2025_new.csv diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cohorts.csv b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cohorts.csv new file mode 100644 index 00000000..a5e9be60 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/cohorts.csv @@ -0,0 +1,27 @@ +skip,cohort,root,wall_type,:wall_base_cavity_insul,:wall_base_cont_insul,:roof_base_cont_insul,:window_u,:window_shgc,:window_transmittance,:floor_base_cont_insul,:office_large_light_area,:kitchen_light_area,:dining_fast_light_area,:classroom_class_light_area,:corridor_light_area,:retail_sales_light_area,:storage_warehouse_light_area,:computer_light_area,:lobby_light_area,:guestroom_light_area,:auditorium_light_area,:conference_light_area,:dining_fine_light_area,:gym_light_area,:restroom_light_area,:health_patient_light_area,:industrial_low_light_area,:laundry_light_area,:auto_light_area,:classroom_shop_light_area,:grocery_light_area,:health_operating_light_area,:industrial_high_light_area,:lab_light_area,:mech_light_area,:office_open_light_area,:storage_refrig_light_area,:office_small_light_area,:main_oa_econ_max_temp +#,Asm&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Asm/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""auditorium"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,ECC&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,ECC/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""computer"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""classroom_shop"", ""LPD"")['W/ft2']",,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,EPr&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,EPr/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,"%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""gym"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,ERC&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,ERC/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,"%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,ESe&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,ESe/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,"%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""computer"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""gym"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,EUn&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,EUn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""computer"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""guestroom"", ""LPD"")['W/ft2']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""industrial_low"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Fin&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Fin/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Gro&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Gro/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""grocery"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""industrial_high"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""storage_refrig"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Hsp&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Hsp/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']",,,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""health_patient"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""health_operating"", ""LPD"")['W/ft2']",,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Htl&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Htl/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""lobby"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""guestroom"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""dining_fine"", ""LPD"")['W/ft2']",,,,,"%= codes.lookup(""Lighting Power Density"", ""laundry"", ""LPD"")['W/ft2']",,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Lib&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Lib/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""conference"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,MBT&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,MBT/templates/root.pxt,Metal Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""computer"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""conference"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""lab"", ""LPD"")['W/ft2']",,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,MLI&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,MLI/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""industrial_low"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Mtl&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Mtl/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,,,"%= codes.lookup(""Lighting Power Density"", ""guestroom"", ""LPD"")['W/ft2']",,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""laundry"", ""LPD"")['W/ft2']",,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Nrs&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Nrs/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""health_patient"", ""LPD"")['W/ft2']",,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,OfL&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,OfL/templates/root.pxt,Metal Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""lobby"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""mech"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""office_open"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,OfS&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,OfS/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""corridor"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""office_small"", ""LPD"")['W/ft2']","%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Rel&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Rel/templates/root.pxt,steel-frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']",,,"%= codes.lookup(""Lighting Power Density"", ""classroom_class"", ""LPD"")['W/ft2']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""auditorium"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RFF&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,RFF/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,"%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""dining_fast"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""lobby"", ""LPD"")['W/ft2']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""restroom"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RSD&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,RSD/templates/root.pxt,Wood Frame,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Wood Framed and Other"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,"%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""lobby"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""dining_fine"", ""LPD"")['W/ft2']",,"%= codes.lookup(""Lighting Power Density"", ""restroom"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +,Rt3&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,Rt3/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RtL&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,RtL/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']","%= codes.lookup(""Lighting Power Density"", ""office_large"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""kitchen"", ""LPD"")['W/ft2']",,,,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,"%= codes.lookup(""Lighting Power Density"", ""auto"", ""LPD"")['W/ft2']",,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,RtS&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,RtS/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,"%= codes.lookup(""Lighting Power Density"", ""retail_sales"", ""LPD"")['W/ft2']","%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,SCn&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,SCn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Metal Framed"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Metal Buildings"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,SUn&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,SUn/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" +#,Wrf&0&cAVVG&New&Chiller __WtrCldCentChlr&WtrCldScrewChlr,WRf/templates/root.pxt,Mass Heavy,"%= codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Cavity R-Value"")['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Walls Above Grade | Mass Heavy"", ""Maximum U-Factor"")-1.49)['R-IP']","%= (1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Roofs | Wood Framed and Other"", ""Maximum U-Factor"")-0.78)['R-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""U-Factor""))['U-IP']","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""SHGC""))","%= (codes.lookup(""Fenestration Requirements | Climate Zone #{climate_zone}"", ""Fixed Window"", ""VT""))","%= ((1/codes.lookup(""Opaque Envelope Requirements | Climate Zone #{climate_zone}"", ""Floors | Other"", ""Maximum U-Factor""))-4.261)['R-IP']",,,,,,,"%= codes.lookup(""Lighting Power Density"", ""storage_warehouse"", ""LPD"")['W/ft2']",,,,,,,,,,,,,,,,,,,,,,"%= codes.lookup(""Economizer Setpoints"", ""#{climate_zone}"", ""Fixed Drybulb"")['F']" diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/query.txt b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/query.txt new file mode 100644 index 00000000..66e76be7 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/SWHC005-05 Water Cooled Chiller_New/query.txt @@ -0,0 +1,30 @@ +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Energy Per Total Building Area/Net Site Energy, Net Site EUI +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Total Energy/Net Site Energy, Net Site Energy +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Total End Uses, Electricity +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Total End Uses, Natural Gas + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Energy Per Total Building Area/Net Source Energy, Net Source EUI +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Total Energy/Net Source Energy, Net Source Energy + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Total End Uses, Total +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heating, Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Cooling, Cooling +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Interior Lighting, Interior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Exterior Lighting, Exterior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Interior Equipment, Interior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Exterior Equipment, Exterior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Fans, Fans +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Pumps, Pumps +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heat Rejection, Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Humidification, Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Heat Recovery, Heat Recovery +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Water Systems, Water Systems +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Refrigeration, Refrigeration +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Total Energy/Generators, Generators + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Heat Rejection, Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Humidification, Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Water/Water Systems, Water Systems + +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Comfort and Setpoint Not Met Summary/Facility/Time Setpoint Not Met During Occupied Heating, Unmet Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Comfort and Setpoint Not Met Summary/Facility/Time Setpoint Not Met During Occupied Cooling, Unmet Cooling diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/global.pxv b/commercial measures/SWHC005-05 Water Cooled Chiller/global.pxv new file mode 100644 index 00000000..c707bb60 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/global.pxv @@ -0,0 +1,2 @@ +:timestep => 6, +:run_control => "ANNUAL" # ANNUAL | SIZING diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/query_wcc.txt b/commercial measures/SWHC005-05 Water Cooled Chiller/query_wcc.txt new file mode 100644 index 00000000..faba355b --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/query_wcc.txt @@ -0,0 +1,38 @@ +ComponentSizingSummary/Entire Facility/Chiller:Electric:EIR/Design Size Reference Capacity/*, Chiller Cooling Capacity +ComponentSizingSummary/Entire Facility/Chiller:Electric:ReformulatedEIR/Design Size Reference Capacity/*, Chiller Cooling Capacity +EquipmentSummary/Entire Facility/Central Plant/IPLV in SI Units/*, IPLV in SI Units +SystemSummary/Entire Facility/Time Setpoint Not Met/During Occupied Heating/, Occupied unmet heating hour +SystemSummary/Entire Facility/Time Setpoint Not Met/During Occupied Cooling/, Occupied unmet cooling hour +InputVerificationandResultsSummary/Entire Facility/General/Value/Program Version and Build +InputVerificationandResultsSummary/Entire Facility/General/Value/Weather File +InputVerificationandResultsSummary/Entire Facility/Zone Summary/Area/Conditioned Total +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Utility Use Per Conditioned Floor Area/Electricity Intensity/HVAC +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Utility Use Per Conditioned Floor Area/Natural Gas Intensity/HVAC +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Cooling +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Interior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Exterior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Interior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Exterior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Fans +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Pumps +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Heat Recovery +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Water Systems +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Refrigeration +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Generators +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Heating +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Cooling +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Interior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Exterior Lighting +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Interior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Exterior Equipment +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Fans +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Pumps +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Heat Rejection +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Humidification +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Heat Recovery +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Water Systems +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Refrigeration +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Generators diff --git a/commercial measures/SWHC005-05 Water Cooled Chiller/rakefile.rb b/commercial measures/SWHC005-05 Water Cooled Chiller/rakefile.rb new file mode 100644 index 00000000..4ed80a71 --- /dev/null +++ b/commercial measures/SWHC005-05 Water Cooled Chiller/rakefile.rb @@ -0,0 +1,1010 @@ +# Copyright (c) 2011-2020 Big Ladder Software LLC. All rights reserved. +# See the file "license.txt" for additional terms and conditions. + +if (not defined?(Modelkit)) + begin + require("modelkit") + rescue LoadError => exception + args = ARGV.join(" ") + puts exception + puts "\e[1m\e[31mERROR: This rakefile requires the Modelkit library. Make sure that you have the\nModelkit gem installed in your local Rubygems environment, or try running the\nrakefile using your stand-alone installation of Modelkit by typing:\e[0m\n \e[1mmodelkit rake #{args}\e[0m" + exit + end +end + + +require("pathname") +require("json") + +require("modelkit/config") +require("modelkit/multitable") +require("modelkit/parametrics") +require("modelkit/parametrics/worksheet") +require("modelkit/energyplus") + + +# Add to modelkit-energyplus: +# other args: +# - which design days +# - water mains temp? +# - daylight saving time? +def generate_site_pxt(idd, ddy_path, site_path) + site_file = File.open(site_path, "w") + + if (File.exists?(ddy_path)) + input_file = OpenStudio::InputFile.open(idd, ddy_path) + else + raise("file not found: #{ddy_path.inspect}") + end + + site_locations = input_file.find_objects_by_class_name("Site:Location").to_a + + if (site_locations.empty?) + raise("could not find Site:Location object in #{ddy_path.inspect}") + else + site_file.puts(site_locations.first.to_idf) + end + + all_design_days = input_file.find_objects_by_class_name("SizingPeriod:DesignDay").to_a + selected_design_days = all_design_days.select { |dd| dd.name[/Ann Htg 99.6% Condns DB|Ann Clg 0?.4% Condns DB/i] } + + if (selected_design_days.length < 2) + puts "warning: could not find requested design days; including all design days\n" + selected_design_days = all_design_days + end + + # Write design days to site file. + selected_design_days.each { |dd| site_file.puts(dd.to_idf) } + + +# 'CorrelationFromWeatherFile' is available starting in EP 9.0. + +# Does this work for design-day only runs? +# Seems to work for annual. + site_file.puts("\n\nSite:WaterMainsTemperature,\n CorrelationFromWeatherFile;\n") + + daylight_saving_time = input_file.find_objects_by_class_name("RunPeriodControl:DaylightSavingTime").to_a + if (not daylight_saving_time.empty?) + site_file.puts + site_file.puts(daylight_saving_time.first.to_idf) + end + + site_file.close +end + + +# NOPUB Should move into Modelkit somewhere. +# Support for running simulations in parallel. +require("open3") +require("set") + +$child_pids = Set.new # Global tracking of child PIDs + +# Return PID? +def run_process(command, dir) + # NOTE: Separate processes are required to make the EnergyPlus runs thread safe! + Open3.popen3(command, :chdir => dir) do |stdin, stdout, stderr, thread| + $child_pids.add(thread.pid) + # This might work with just an instance variable or similar. + + stdin.close # All input already sent with command + + file_out = File.open("#{dir}/stdout", "w") + file_err = File.open("#{dir}/stderr", "w") + + while (line = stdout.gets) + file_out.puts(line) + #@proc_out.call(line) if (@proc_out) + end + + # This is probably not right. + while (line = stderr.gets) + file_err.puts(line) + #@proc_err.call(line) if (@proc_err) + end + + stdout.close + stderr.close + + file_out.close + file_err.close + + #print "Completed: #{File.basename(dir)}\n" + $child_pids.delete(thread.pid) + end +end + +# Search up through parent directories for one or more possible file names. +def search_parent_dirs(start_dir, *file_names) + path = nil + dir_names = start_dir.to_s.split("/") + while (not dir_names.empty?) do + file_names.each do |file_name| + test_path = "#{dir_names.join("/")}/#{file_name}" + if (File.exist?(test_path)) + path = test_path + break + end + end + break if (path) + dir_names.pop + end + return(path) +end + +# Search for a file name or partial path in an array of provided directories. +# Directories are expected to already be absolute paths. +def resolve_path(path, dirs) + resolved_path = nil + dirs.each do |dir| + expanded_path = File.expand_path(path, dir) + if (File.exist?(expanded_path)) + resolved_path = expanded_path + break + end + end + return(resolved_path) +end + +# Clean up any previous output files left behind if 'compose' or 'run' fails. +# Leftover files can be processed unintentionally by downstream tasks and +# ultimately generate false results. +def clean_energyplus_output_files(dir) + # Not all of these files might be present. Others might be present and unhandled. + paths = [ + "#{dir}/instance-out.err", + "#{dir}/instance-out.rdd", + "#{dir}/instance-out.sql", # Most important for downstream tasks + "#{dir}/instance-tbl.htm", + "#{dir}/instance-var.csv", + "#{dir}/stderr", + "#{dir}/stdout" + ] + FileUtils.rm_f(paths) +end + + +# Rake stubbornly sets the working directory to wherever the Rakefile is located. +# The target directory could optionally be set from a CLI option instead. +study_dir = Rake.application.original_dir + +climates_csv_path = "#{study_dir}/climates.csv" +cohorts_csv_path = "#{study_dir}/cohorts.csv" + +query_path = "#{study_dir}/query.txt" +results_summary_path = "#{study_dir}/results-summary.csv" +results_profile_elec_path = "#{study_dir}/results-profile-elec.csv" +results_profile_gas_path = "#{study_dir}/results-profile-gas.csv" +results_paths = [results_summary_path, results_profile_elec_path, results_profile_gas_path] + +cases_dir = "#{study_dir}/cases" +runs_dir = "#{study_dir}/runs" +runs_pathname = Pathname.new(runs_dir) + +MUTEX = Mutex.new # Thread lock for when something needs to run in a single thread + +config_path = search_parent_dirs(study_dir, ".modelkit-config") +if (not config_path) + raise("modelkit-config file not found in working directory or any parent directory") +else + CONFIG = Modelkit::Config.new(config_path) + puts "Using modelkit-config at #{config_path}\n" +end + +config = Hash.new +[:prototypes_dir, :templates_dir, :weather_dir, :codes_dir].each do |key| + config[key] = [] + field = key.to_s.gsub(/_/, "-") + if (not CONFIG[field]) + raise("#{field} variable missing in modelkit-config") + else + config_paths = CONFIG[field].split(/\s*;\s*/) # Split string with semicolons into array of paths + config_paths.each do |path| + # Resolve path relative to modelkit-config file and normalize the slashes. + config[key] << File.expand_path(path.strip.gsub(/\\/, "/"), File.dirname(config_path)) + end + end +end + +max_workers = CONFIG["max-workers"] +if (max_workers.nil?) + max_workers = 1 +end + +global_pxv_path = search_parent_dirs(study_dir, "global.pxv") +if (global_pxv_path) + puts "Using global.pxv at #{global_pxv_path}\n" +end + +rake_tasks = Rake.application.top_level_tasks +rake_task_name = rake_tasks.first # Multiple tasks are allowed, but assume one + +rake_options = Rake.application.options +rake_options.always_multitask = true # --multitask, -m +#rake_options.job_stats = true # --job-stats true | :history +rake_options.thread_pool_size = max_workers - 1 # --jobs, -j (default 12 on Mac) + +if (rake_options.dryrun or rake_options.show_all_tasks or + rake_options.show_prereqs or rake_options.show_tasks) + # These are information-only requests. Rake nonetheless registers as invoked + # with the "default" task name but nothing actually gets run. + rake_task_name = "none" +end + + +# Show threads message and info about how to change +# Running with 8 threads (edit .modelkit-config to change). +# Type Ctrl+C to cancel all tasks. + +require "io/console" # need this anyway for progress bar + +#$stdin.echo = false # turn off echo; in Mac shows a cursor with a key icon +# This prevents the user from over-typing the output stream. + +# also try switching to raw mode--should also block user input; maybe no key icon? + +#print "\e[?25l" # hide the cursor; MUST remember to show it again on exit or else it's permanent for the session! + + +trap("INT") do # Ctrl+C (polite kill) + puts "Canceling all tasks.\n" + if ($child_pids) + $child_pids.each { |pid| Process.kill("KILL", pid) } + end + exit +end + +if (Modelkit::Platform.unix?) + trap("TSTP") do # Ctrl+Z (suspend) + puts "Suspending all tasks. Type 'fg' to resume.\n" + exit + end +end + +if (not rake_task_name =~ /^(prune|clean|none)$/) + +# If possible, detect if any tasks will be run before showing this message: +puts "\e[1mType Ctrl+C to cancel all tasks.\e[0m\n" + +end + +# modelkit rake -A crashes for some reason + +# NOPUB Some of above could be included here too. +# Don't evaluate worksheets and generate file tasks if not necessary! +# NOTE: prune does need to evaluate worksheets. +if (not rake_task_name =~ /^(clean|none)$/) + + pxv_paths = [] + site_paths = [] + + compose_idf_paths = [] + + + #rename size_ to sizerun_ size_run_ sizing_run_ + size_ref_paths = [] + size_idf_paths = [] + size_sql_paths = [] + size_json_paths = [] + + hardsize_idf_paths = [] + + run_sql_paths = [] + run_csv_paths = [] + + + + old_site_paths = Dir.glob("#{runs_dir}/*/site.pxt") + old_pxv_paths = Dir.glob("#{runs_dir}/**/instance.pxv") + + climates = Modelkit::Worksheet.open(climates_csv_path) + cohorts = Modelkit::Worksheet.open(cohorts_csv_path) + + climate_pattern = ENV["CLIMATE"] || "" + + new_case_csv = "skip,case_name\n,defaults\n" # Could be read from config instead + + cohorts_first_pass = true + + puts "Evaluating worksheets...\n" + + csv_table = climates.each_row do |row1, index1, variables1, parameters1| + #puts "climate_index = #{index1}" + + if (not variables1.key?(:climate)) + raise("required column \"climate\" is missing in #{File.basename(climates_csv_path)}") + end + + climate_name = variables1[:climate].to_s.strip # Could have been converted to non-string by Util.value_from_string + if (climate_name.empty?) + raise("climate field cannot be blank for row #{index1 + 2} of #{File.basename(climates_csv_path)}") + end + + next if (not climate_name =~ Regexp.new(climate_pattern)) + + FileUtils.mkdir_p("#{runs_dir}/#{climate_name}") + + site_path = "#{runs_dir}/#{climate_name}/site.pxt" + if (site_paths.include?(site_path)) + puts "warning: duplicate name #{climate_name.inspect} in climate column at row #{index1 + 2} in #{File.basename(climates_csv_path)}; row will be skipped" + next + end + + site_paths << site_path + + if (not variables1.key?(:weather_file)) + raise("required column \"weather_file\" is missing in #{File.basename(climates_csv_path)}") + end + + weather_name = variables1[:weather_file].to_s.strip # Could have been converted to non-string by Util.value_from_string + if (weather_name.empty?) + raise("weather_file field cannot be blank for row #{index1 + 2} of #{File.basename(climates_csv_path)}") + end + + epw_path = resolve_path(weather_name, config[:weather_dir]) + if (not epw_path) + puts "Could not resolve path #{weather_name.inspect} from possible paths:\n" + config[:weather_dir].each { |dir| puts " #{File.expand_path(weather_name, dir).inspect}\n" } + puts "Check the weather-dir variable in modelkit-config file.\n" + raise("weather file #{weather_name.inspect} not found for row #{index1 + 2} of #{File.basename(climates_csv_path)}") + end + + if (not File.file?(epw_path)) + raise("weather file #{epw_path.inspect} is not a file for row #{index1 + 2} of #{File.basename(climates_csv_path)}") + end + + ddy_path = "#{File.dirname(epw_path)}/#{File.basename(epw_path, ".*")}.ddy" # Ensure ddy is from same directory as resolved epw file + if (not File.exist?(ddy_path)) + puts "Weather file path resolved to #{epw_path.inspect}\n" + raise("ddy file #{ddy_path.inspect} not found for row #{index1 + 2} of #{File.basename(climates_csv_path)}") + end + + # This file only exists to indicate if the weather file changes for dependency purposes. + # The weather file is the one input that is separate from instance parameters. + weather_path = "#{runs_dir}/#{climate_name}/weather" + pathname = Pathname.new(weather_path).relative_path_from(runs_pathname) + + if (File.exist?(weather_path)) + old_epw_path = File.read(weather_path) + if (epw_path != old_epw_path) + puts "Updating: #{pathname}\n" + File.write(weather_path, epw_path) + end + else + puts "Writing: #{pathname}\n" + File.write(weather_path, epw_path) + end + + # generate site.pxt from .ddy file + file site_path => [weather_path, ddy_path] do + idd = open_data_dictionary + pathname = Pathname.new(site_path).relative_path_from(runs_pathname) + puts "Generating: #{pathname}\n" + generate_site_pxt(idd, ddy_path, site_path) + end + + if (variables1.key?(:codes_file)) # NOTE: codes_file is an optional column + codes_name = variables1[:codes_file].to_s.strip # Could have been converted to non-string by Util.value_from_string + if (codes_name.empty?) + raise("codes_file field cannot be blank for row #{index1 + 2} of #{File.basename(climates_csv_path)}") + end + + codes_path = resolve_path(codes_name, config[:codes_dir]) + if (not codes_path) + puts "Could not resolve path #{codes_name.inspect} from possible paths:\n" + config[:codes_dir].each { |dir| puts " #{File.expand_path(codes_name, dir).inspect}\n" } + puts "Check the codes-dir variable in modelkit-config file.\n" + raise("codes file #{codes_name.inspect} not found for row #{index1 + 2} of #{File.basename(climates_csv_path)}") + end + + if (not File.file?(codes_path)) + raise("codes file #{codes_path.inspect} is not a file for row #{index1 + 2} of #{File.basename(climates_csv_path)}") + end + + codes_table = Modelkit::MultiTable.new(codes_path) + + else + codes_table = nil # Must set something to pass to next worksheet + end + + variables1[:codes] = codes_table # For backwards compatibility + + # Make sure objects passed in are not mutated by the Worksheet. Make dupes? + + cohort_names = [] # Accumulate names to check for duplicates + + cohorts.each_row(variables1) do |_, index2, variables2, parameters2| + #puts " cohort_index = #{index2}" + + # NOTE: Variables from outer worksheet (variables1) are copied into this worksheet. + # Changes to the variables here (variables2) do not propagate back up. + + if (not variables2.key?(:cohort)) + raise("required column \"cohort\" is missing in #{File.basename(cohorts_csv_path)}") + end + + cohort_name = variables2[:cohort].to_s.strip # Could have been converted to non-string by Util.value_from_string + if (cohort_name.empty?) + raise("cohort field cannot be blank for row #{index2 + 2} of #{File.basename(cohorts_csv_path)}") + end + + if (cohort_names.include?(cohort_name)) + if (cohorts_first_pass) # Only warn about this row once + puts "warning: duplicate name #{cohort_name.inspect} in cohort column at row #{index2 + 2} in #{File.basename(cohorts_csv_path)}; row will be skipped" + end + next + end + + cohort_names << cohort_name + + cases_csv_path = "#{cases_dir}/#{cohort_name}.csv" + cases_csv_short_path = "#{File.basename(cases_dir)}/#{cohort_name}.csv" + if (not File.exist?(cases_csv_path)) + puts("Cases worksheet #{cases_csv_short_path.inspect} not found for row #{index2 + 2} of #{File.basename(cohorts_csv_path)}\n") + puts("Creating: #{cases_csv_short_path}\n") + FileUtils.mkdir_p(cases_dir) + File.write(cases_csv_path, new_case_csv) + end + + if (not variables2.key?(:root)) + raise("required column \"root\" is missing in #{File.basename(cohorts_csv_path)}") + end + + root_name = variables2[:root].to_s.strip # Could have been converted to non-string by Util.value_from_string + if (root_name.empty?) + raise("root field cannot be blank for row #{index2 + 2} of #{File.basename(cohorts_csv_path)}") + end + + root_path = resolve_path(root_name, config[:prototypes_dir]) + if (not root_path) + puts "Could not resolve path #{root_name.inspect} from possible paths:\n" + config[:prototypes_dir].each { |dir| puts " #{File.expand_path(root_name, dir).inspect}\n" } + puts "Check the prototypes-dir variable in modelkit-config file.\n" + raise("root template #{root_name.inspect} not found for row #{index2 + 2} of #{File.basename(cohorts_csv_path)}") + end + + if (not File.file?(root_path)) + raise("root template #{root_path.inspect} is not a file for row #{index2 + 2} of #{File.basename(cohorts_csv_path)}") + end + + case_names = [] # Accumulate names to check for duplicates + + # Better to pre-read and cache this outside the looping? + # There are only N worksheets...1 per building type. + cases = Modelkit::Worksheet.open(cases_csv_path) + + cases.each_row(variables2) do |_, index3, variables3, parameters3| + #puts " case_index = #{index3}" + + # NOTE: Variables from outer worksheet (variables2) are copied into this worksheet. + # Changes to the variables here (variables3) do not propagate back up. + + if (not variables3.key?(:case_name)) + raise("required column \"case_name\" is missing in #{File.basename(cases_dir)}/#{File.basename(cases_csv_path)}") + end + + case_name = variables3[:case_name].to_s.strip # Could have been converted to non-string by Util.value_from_string + if (case_name.empty?) + raise("case_name field cannot be blank for row #{index3 + 2} of #{File.basename(cases_dir)}/#{File.basename(cases_csv_path)}") + end + + if (case_names.include?(case_name)) + if (cohorts_first_pass) # Only warn about this row once + puts "warning: duplicate name #{case_name.inspect} in case_name column at row #{index3 + 2} in #{File.basename(cases_dir)}/#{File.basename(cases_csv_path)}; row will be skipped" + end + next + end + + case_names << case_name + run_name = "#{climate_name}/#{cohort_name}/#{case_name}" + case_dir = "#{runs_dir}/#{run_name}" + FileUtils.mkdir_p(case_dir) + + # better to create this dynamically in cases.csv by combining variables from other layers. + # all variables need to be propagated first from layer to layer. + # for example: + # :run_name + # %= "My Prefix Something: #{climate}/#{cohort}/#{case_name}" + pxv_string = ":run_name => #{run_name.inspect},\n" + + parameters = parameters1 | parameters2 | parameters3 + parameters.each do |key, value| + value_inspect = value.inspect + if (value.kind_of?(String)) + # Using `inspect` on strings is useful because it reveals invisible + # characters and invalid byte sequences. The downside is that the + # string must be unescaped. + value_inspect.gsub!(/\\\\/, "\\") + end + pxv_string << ":#{key} => #{value_inspect},\n" + end + + pxv_path = "#{case_dir}/instance.pxv" + pxv_paths << pxv_path + + pathname = Pathname.new(pxv_path).relative_path_from(runs_pathname) + + if (File.exist?(pxv_path)) + old_pxv_string = File.read(pxv_path) + if (pxv_string != old_pxv_string) + puts "Updating: #{pathname}\n" + File.write(pxv_path, pxv_string) + end + else + puts "Writing: #{pathname}\n" + File.write(pxv_path, pxv_string) + end + + compose_idf_path = "#{case_dir}/instance.idf" + compose_idf_paths << compose_idf_path + + if (variables3[:sizing_case]) + size_name = "#{climate_name}/#{cohort_name}/#{variables3[:sizing_case]}" + size_dir = "#{runs_dir}/#{size_name}" + size_ref_path = "#{size_dir}/instance.idf" + + size_idf_path = "#{size_dir}/instance-size.idf" + size_sql_path = "#{size_dir}/instance-size-out.sql" + size_json_path = "#{size_dir}/instance-size-out.json" + + if (size_ref_paths.include?(size_ref_path)) + # Avoid creating redundant tasks when multiple cases reference same sizing case. + create_sizing_tasks = false + else + create_sizing_tasks = true + + size_ref_paths << size_ref_path + size_idf_paths << size_idf_path + size_sql_paths << size_sql_path + size_json_paths << size_json_path + end + + hardsize_idf_path = "#{case_dir}/instance-hardsize.idf" + hardsize_idf_paths << hardsize_idf_path + + run_idf_path = hardsize_idf_path # Which input file to run + + run_sql_path = "#{case_dir}/instance-hardsize-out.sql" + run_sql_paths << run_sql_path + + run_csv_path = "#{case_dir}/instance-hardsize-var.csv" + run_csv_paths << run_csv_path + + else + # Autosize-only run. + size_ref_path = nil + + run_idf_path = compose_idf_path # Which input file to run + + run_sql_path = "#{case_dir}/instance-out.sql" + run_sql_paths << run_sql_path + + run_csv_path = "#{case_dir}/instance-var.csv" + run_csv_paths << run_csv_path + end + + # Compose input file from parameter file. + # need more dependencies here: template files + file compose_idf_path => [site_path, root_path, pxv_path, global_pxv_path].compact do # If no path for global.pxv, remove nil element + pathname = Pathname.new(compose_idf_path).relative_path_from(runs_pathname) + puts "Composing: #{pathname}\n" + + clean_energyplus_output_files(File.dirname(compose_idf_path)) + + site_dir = File.dirname(site_path) + + begin + Modelkit::Parametrics.template_compose(root_path, + :annotate => CONFIG["template-compose.annotate"], + :indent => CONFIG["template-compose.indent"], + :esc_line => CONFIG["template-compose.esc-line"], + :dirs => [site_dir, *config[:templates_dir]], + :files => [global_pxv_path, pxv_path].compact, # If no path for global.pxv, remove nil element + :output => compose_idf_path) + rescue Exception => exception + puts "#{exception.class.name}: #{exception.message}\n" + puts "#{exception.backtrace.first}\n" if (not SyntaxError === exception) + puts "Skipping: #{pathname}\n" + end + end + + if (create_sizing_tasks) + # Generate a modified input file in order to run a design-day-only simulation. + # NOTE: This can be eliminated if a design-day option is added to energyplus-run. + file size_idf_path => size_ref_path do + pathname = Pathname.new(size_idf_path).relative_path_from(runs_pathname) + puts "Generating size run: #{pathname}\n" + + FileUtils.cp(size_ref_path, size_idf_path) + + idd = open_data_dictionary + input_file = OpenStudio::InputFile.open(idd, size_idf_path) + + sc_objs = input_file.find_objects_by_class_name("SimulationControl") + if sc_objs.length != 1 + raise "More than one SimulationControl object found" + end + sc = sc_objs[0] + sc.fields[1] = "Yes" + sc.fields[2] = "Yes" + sc.fields[3] = "Yes" + sc.fields[4] = "Yes" + sc.fields[5] = "No" + + input_file.write(size_idf_path) + end + + # Run sizing input files for design days only. + file size_sql_path => size_idf_path do + pathname = Pathname.new(size_idf_path).relative_path_from(runs_pathname) + puts "Running size run: #{pathname}\n" + + command = "modelkit-energyplus energyplus-run --weather=\"#{epw_path}\" \"#{size_idf_path}\"" + run_process(command, size_dir) + end + + # Generate size data file (instance-size-out.json). + file size_json_path => size_sql_path do + pathname = Pathname.new(size_json_path).relative_path_from(runs_pathname) + puts "Extracting size data: #{pathname}\n" + + # Make a copy to work on because the original gets overwritten by EnergyPlus.size. + temp_path = "#{File.dirname(size_idf_path)}/instance-temp.idf" + FileUtils.cp(size_idf_path, temp_path) + + idd = open_data_dictionary + input_file = OpenStudio::InputFile.open(idd, temp_path) + sql = Modelkit::EnergyPlus::SQLOutput.new(size_sql_path) + + # This will be fixed to only generate JSON and not modify the input file. + _, count, output_file = Modelkit::EnergyPlus.size( + sql, input_file, {json: size_json_path, version: "9-2"}) + #puts("#{count} modifications made") + + FileUtils.rm_f(temp_path) + end + end + + if (hardsize_idf_path) + # This would be a reasonable place to use `multitask` because compose_idf_path and + # size_json_path are independent and can be run concurrently. However, it seems + # like `multitask` doesn't compare timestamps like `file` does. Instead it + # always runs like a regular `task`. + file hardsize_idf_path => [compose_idf_path, size_json_path] do + pathname = Pathname.new(hardsize_idf_path).relative_path_from(runs_pathname) + puts "Applying hard sizes: #{pathname}\n" + + idd = open_data_dictionary + input_file = OpenStudio::InputFile.open(idd, compose_idf_path) + + json_string = File.read(size_json_path) + value_map = JSON.parse(json_string, {:symbolize_names=>true}) + output_file, count = Modelkit::EnergyPlus.modify_objects(input_file, value_map) + #puts("#{count} modifications made") + + # Set SimulationControl fields 1, 2, and 3 to "No", "No", and "No" + sc_objs = output_file.find_objects_by_class_name("SimulationControl") + if sc_objs.length != 1 + raise "More than one SimulationControl object found" + end + sc = sc_objs[0] + sc.fields[1] = "No" + sc.fields[2] = "No" + sc.fields[3] = "No" + # Remove Sizing:Zone and Sizing:System objects + sizing_zones = output_file.find_objects_by_class_name("Sizing:Zone") + sizing_systems = output_file.find_objects_by_class_name("Sizing:System") + sizing_plants = output_file.find_objects_by_class_name("Sizing:Plant") + (sizing_zones + sizing_systems + sizing_plants).each {|x| output_file.delete_object(x)} + + output_file.write(hardsize_idf_path) + end + end + + # Run input file in a separate process. + file run_sql_path => [epw_path, run_idf_path] do + # Not sure why this check is needed; seems to try to run if even IDF does not exist. + # May need in other places, like sizing run. + next if (not File.exist?(run_idf_path)) + + pathname = Pathname.new(run_idf_path).relative_path_from(runs_pathname) + puts "Running: #{pathname}\n" + + # Because this is spawned to the shell, .modelkit-config options will be + # automatically applied. + # NOTE: If modelkit-energyplus was thread safe, would not have to run this + # as a separate process. + command = "modelkit-energyplus energyplus-run --weather=\"#{epw_path}\" \"#{run_idf_path}\"" + run_process(command, case_dir) + #$bar.inc + end + + + # see discussion with Michael + file run_csv_path => run_sql_path + + # deleting instance-out.csv breaks it; doesn't know how to recover + + end + end + + cohorts_first_pass = false + end + + + prune_paths = (old_site_paths - site_paths) + (old_pxv_paths - pxv_paths) + + if (not prune_paths.empty? and not rake_task_name =~ /^(prune|clean|none)$/) + puts "\e[1m\e[33mNote: There are cases in the runs directory that are not referenced by any\n" \ + "worksheet. You may want to delete them by typing:\e[0m\n \e[1mmodelkit rake prune\e[0m\n" + end + +end + + +desc "Generate case files" +task :cases do + # No operation; cases are generated when worksheets are evaluated. +end + + +desc "Delete unreferenced files" +task :prune do + if (prune_paths.empty?) + puts "Prune has nothing to delete." + else + prune_dirs = [] + puts "\e[1m\e[31mPrune will delete the following files:\e[0m" + +# show each as: dirname/* (106 files) + + prune_paths.each do |path| + dir = File.dirname(path) + prune_dirs << dir + pathname = Pathname.new(dir).relative_path_from(runs_pathname) + puts " \e[31m#{pathname}\e[0m" + end + print "\e[1m\e[31mConfirm (y/n)?\e[0m " + + input = ENV["CONFIRM"] || $stdin.gets || "" + if (ENV["CONFIRM"] or not $stdin.tty?) + puts input # Echo when not already written to STDOUT + end + + $start_time = Time.now # Reset to cut out wait time on the user prompt + if (input.strip =~ /^y/i) + puts "Pruning files..." + + # maybe don't have to repeat this--already said what was to be deleted + prune_dirs.each do |dir| + pathname = Pathname.new(dir).relative_path_from(runs_pathname) + puts "Deleting: #{pathname}" + FileUtils.rm_rf(dir) + end + else + puts "Task canceled." + end + end +end + + +desc "Delete all files and results" +task :clean do + paths = []; names = [] + [runs_dir, *results_paths].each do |path| + if (File.directory?(path)) + count = Dir.glob("#{path}/**/*").count { |f| File.file?(f) } + if (count.nonzero?) + paths << Dir.glob("#{path}/*") + names << "#{File.basename(path)}/* (#{count} files)" + end + elsif (File.file?(path)) + paths << path + names << File.basename(path) + end + end + + if (paths.empty?) + puts "Clean has nothing to delete." + else + puts "\e[1m\e[31mClean will delete the following files:\e[0m" + names.each { |name| puts " \e[31m#{name}\e[0m"} + print "\e[1m\e[31mConfirm (y/n)?\e[0m " + + input = ENV["CONFIRM"] || $stdin.gets || "" + if (ENV["CONFIRM"] or not $stdin.tty?) + puts input # Echo when not already written to STDOUT + end + + $start_time = Time.now # Reset to cut out wait time on the user prompt + if (input.strip =~ /^y/i) + puts "Cleaning files..." + FileUtils.rm_rf(paths) + else + puts "Task canceled." + end + end +end + + +desc "Generate site files (site.pxt)" +multitask :sites => site_paths + + +desc "Compose input files" +multitask :compose => compose_idf_paths + + +# Generate size input files +multitask :"size-idf" => size_idf_paths + + +# Run size input files +multitask :"size-sql" => size_sql_paths + + +# Extract size data +multitask :"size-json" => size_json_paths + + +desc "Apply hard sizes to input files" +multitask :hardsize => hardsize_idf_paths + + +desc "Run input files" +multitask :run => run_sql_paths + + +file query_path do + puts "Query file not found.\n" + query = +"AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Energy Per Total Building Area/Net Site Energy, Net Site EUI +AnnualBuildingUtilityPerformanceSummary/Entire Facility/Site and Source Energy/Total Energy/Net Site Energy, Net Site Energy +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Electricity/Total End Uses, Electricity +AnnualBuildingUtilityPerformanceSummary/Entire Facility/End Uses/Natural Gas/Total End Uses, Natural Gas\n" + File.write(query_path, query) + puts "Writing default query file: #{query_path}\n" +end + + +file results_summary_path => [*run_sql_paths, query_path] do + pathname = Pathname.new(results_summary_path).relative_path_from(Pathname.new(study_dir)) + puts "Processing: #{pathname}\n" + + short_paths = run_sql_paths.map { |path| Pathname.new(path).relative_path_from(runs_pathname) } + Modelkit::EnergyPlus.sql(short_paths, query_path, :dir => runs_dir, :output => results_summary_path) +end + + +file results_profile_elec_path => run_csv_paths do + aggregate_profiles("Electricity:Facility", results_profile_elec_path, run_csv_paths, runs_pathname, study_dir) +end + + +file results_profile_gas_path => run_csv_paths do + aggregate_profiles("Gas:Facility", results_profile_gas_path, run_csv_paths, runs_pathname, study_dir) +end + + +desc "Aggregate the simulation results" +task :results => results_paths + + +task :default => :results + + +def aggregate_profiles(column_name, output_path, run_csv_paths, runs_pathname, study_dir) + pathname = Pathname.new(output_path).relative_path_from(Pathname.new(study_dir)) + puts "Processing: #{pathname}\n" + + short_paths = run_csv_paths.map { |path| Pathname.new(path).relative_path_from(runs_pathname) } + + columns = [] + column_header = nil + date_time = true + short_paths.each do |short_path| + csv_path = "#{runs_pathname}/#{short_path}" + if (File.exist?(csv_path)) + csv = CSV.read(csv_path, :headers=>true) + if (date_time) + column = csv["Date/Time"] + column.unshift("Date/Time") # Add header + columns << column + date_time = false + end + if (not column_header) + # Match column name to the header while ignoring units/interval, i.e., [J](Hourly). + column_header = csv.headers.find { |header| header.match(column_name) } + end + column = csv[column_header] + column.unshift(short_path) # Add header + columns << column + else + puts "warning: file not found: #{csv_path}\n" + end + end + + File.open(output_path, "w") do |file| + columns.transpose.each { |row| file.puts(row.join(",")) } + end +end + + +# NOPUB consider building this into modelkit-energyplus. +# basically caches IDD path and avoids concurrent openings. + +# Open the EnergyPlus IDD if needed, but only do it once. +def open_data_dictionary + MUTEX.synchronize do # Lock to prevent opening multiple times concurrently + if (@idd.nil?) + puts "Opening Energy+.idd...\n" + + if (path = CONFIG["energyplus-run.engine"]) + path = File.expand_path(path.gsub(/\\/, "/")) # Resolve path and normalize + if (File.exist?(path)) + idd_path = "#{path}/Energy+.idd" + if (not File.exist?(idd_path)) + raise("Energy+.idd not found in specified EnergyPlus directory: #{path}") + end + else + raise("EnergyPlus directory not found: #{path}") + end + else + raise("energyplus-run.engine field missing in .modelkit-config") + end + + @idd = OpenStudio::DataDictionary.open(idd_path) + end + end + return(@idd) +end + + +# NICE, works +#require "rake/cpu_counter" +#puts "cpu=#{Rake::CpuCounter.count}" + +# Almost works but not quite: + +# shows what command was invoked from CLI +# if blank (even with -T), it's "default". +#puts "top level:" +# cli_tasks = Rake.application.top_level_tasks +# cli_task_name = cli_tasks.first # could be more than one; just grab first for now +# puts "cli_task_name=#{cli_task_name}" # returns String + +# cli_task = Rake.application.tasks.find { |t| t.name == cli_task_name } # returns Rake::Task +# puts "cli_task=#{cli_task}" +# + +# +## Rake has this builtin: +# Rake.application.lookup(task_name) => task + +# work_to_do = false +# if (cli_task.needed?) +# # Just because needed doesn't mean there is any work to do--check prereqs! +# cli_task.prerequisite_tasks.each do |prereq| +# if (prereq.needed?) +# work_to_do = true +# break +# end +# end +# end +# +# if (work_to_do) +# puts "Work to do!" +# else +# puts "Up to date; nothing to do." +# end + + +$start_time = Time.now +#$bar = RakeProgressbar.new(run_sql_paths.length) + +at_exit do + #$bar.finished + if (not rake_task_name =~ /^none$/) + puts "Elapsed task duration: #{Time.now - $start_time} sec" + end +end diff --git a/templates/energyplus/templates/system/chw.pxt b/templates/energyplus/templates/system/chw.pxt index 53e927a8..289dd1e5 100644 --- a/templates/energyplus/templates/system/chw.pxt +++ b/templates/energyplus/templates/system/chw.pxt @@ -31,8 +31,12 @@ parameter "chiller_generator_type", :default=>"HOTWATER" # For absorption chill # NOTE: If DIRECTFIRED is selected, the heating_source must be set to "ABSORPTIONCHILLER" for hotwater.imf. parameter "num_chillers", :default=>1 -parameter "chiller_model", :default=>"TRANE_RTAA_125" # (TRANE_RTAA_125 | TRANE_CGA_120 | Air-Cooled GTE 150tons Default 90.1-2004 | WC Screw Default 90.1-2004 | WC Centrifugal Default 90.1-2004 | AC 2010 | AC 2004 | WC Cent 2010 A | WC Cent 2010 B | WC Cent 2004 Small | WC Cent 2004 Large | WC PD 2010 B | WC PD 2010 A Small | WC PD 2010 A Large | WC PD 2004 ) +parameter "chiller_model", :default=>"TRANE_RTAA_125" # (Model 9 WC Chiller | Model 7 WC Chiller | TRANE_RTAA_125 | TRANE_CGA_120 | Air-Cooled GTE 150tons Default 90.1-2004 | WC Screw Default 90.1-2004 | WC Centrifugal Default 90.1-2004 | AC 2010 | AC 2004 | WC Cent 2010 A | WC Cent 2010 B | WC Cent 2004 Small | WC Cent 2004 Large | WC PD 2010 B | WC PD 2010 A Small | WC PD 2010 A Large | WC PD 2004) + # Solaris - 2024-06-12 Added two more water cooled chiller (Model 9 WC Chiller | Model 7 WC Chiller) + # Solaris(Behzad S. Rizi) - 2024-08-09 & 2024-08-22 Added two water cooled chiller models for the basecases(ElectricEIR & ReformulatedEIR)>>>(ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD & ReformEIRChiller Carrier 19XR 1234kW/5.39COP/VSD | ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve & ReformEIRChiller Trane RTHB 1051kW/5.05COP/Valve) parameter "chiller_cop", :default=>2.87 # Chiller nominal COP + # Solaris - 2024-06-12 Added more chiller nominal COP for water-cooled chiller reformulated EIR (4.8 | 5.0 | 5.4 | 5.6 | 6.0 | 6.1 | 6.4 | 6.5) +parameter "wc_option", :default=>"Reformulated" # (EIR | Reformulated) parameter "chiller_sizing", :default=>1.0 # Chiller sizing factor (formerly to counteract oversizing problem; as of 7.2 chiller seems to undersize) parameter "chiller_condenser", :default=>"AIRCOOLED" # Chiller condenser type (AIRCOOLED | WATERCOOLED | EVAPCOOLED) parameter "chiller_heatpump_hr", :default=>false # Chiller heat pump heat recovery @@ -61,7 +65,7 @@ parameter "hi_outdoor_temp", :default=>80['F'] # Outside air high temperature f parameter "chw_temp_ref", :default=>6.67['C'] # Reference Leaving Chilled Water Temperature parameter "cw_temp_ref", :default=>34.4444['C'] # Reference Leaving Condenser Water Temperature - +parameter "chiller_plr_curve", :default=>"ChillerPartLoadWithLift" # Chiller PLR Curve (ChillerPartLoadWithLift | Bicubic | Quadratic) parameter "operation_schedule", :default => "Through: 12/31,\n For: AllDays,\n Until: 24:00, 1;" %> @@ -310,7 +314,11 @@ PlantEquipmentList, <% if (cooling_source == "CHILLER") %> <% if (chiller_type == "ELECTRIC") %> <% if (chiller_condenser == "WATERCOOLED") %> + <% if (wc_option == "EIR") %> + Chiller:Electric:EIR, !- Equipment 1 Object Type + <% else %> Chiller:Electric:ReformulatedEIR, !- Equipment 1 Object Type + <% end %> <% else %> Chiller:Electric:EIR, !- Equipment 1 Object Type <% end %> @@ -330,7 +338,11 @@ PlantEquipmentList, <% for i in (1..num_chillers-1) %> <%= name %> Chiller <%= i %>, !- Equipment 1 Name <% if (chiller_condenser == "WATERCOOLED") %> + <% if (wc_option == "EIR") %> + Chiller:Electric:EIR, !- Equipment 2 Object Type + <% else %> Chiller:Electric:ReformulatedEIR, !- Equipment 2 Object Type + <% end %> <% else %> Chiller:Electric:EIR, !- Equipment 2 Object Type <% end %> @@ -502,7 +514,11 @@ Branch, <% if (cooling_source == "CHILLER") %> <% if (chiller_type == "ELECTRIC") %> <% if (chiller_condenser == "WATERCOOLED") %> + <% if (wc_option == "EIR") %> + Chiller:Electric:EIR, !- Component 1 Object Type + <% else %> Chiller:Electric:ReformulatedEIR, !- Component 1 Object Type + <% end %> <% else %> Chiller:Electric:EIR, !- Component 1 Object Type <% end %> @@ -524,7 +540,9 @@ Branch, <% if (cooling_source == "CHILLER") %> <% if (chiller_type == "ELECTRIC") %> + <% if (chiller_condenser == "WATERCOOLED") %> +<% if (wc_option == "Reformulated") %> Chiller:Electric:ReformulatedEIR, <%= name %> Chiller <%= i %>, !- Name Autosize, !- Reference Capacity {W} @@ -535,7 +553,12 @@ Chiller:Electric:ReformulatedEIR, Autosize, !- Reference Condenser Water Flow Rate {m3/s} <%= name %> Chiller Cap Curve, !- Cooling Capacity Function of Temperature Curve Name <%= name %> Chiller EIR Curve, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name + !Behzad Rizi - 2024-06-17 - Changed LeavingCondenserWaterTemperature to Lift +<% if (chiller_plr_curve == "ChillerPartLoadWithLift") %> + Lift, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Type +<% else %> LeavingCondenserWaterTemperature, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Type +<% end %> <%= name %> Chiller PLR Curve, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.1, !- Minimum Part Load Ratio {} 1.0, !- Maximum Part Load Ratio {} @@ -560,8 +583,50 @@ Branch, <%= name %> Chiller <%= i %>, !- Component 1 Name <%= name %> Chiller <%= i %> Water Inlet Node, !- Component 1 Inlet Node Name <%= name %> Chiller <%= i %> Water Outlet Node; !- Component 1 Outlet Node Name + + <% else %> +# if cw_option is "EIR" +Chiller:Electric:EIR, + <%= name %> Chiller <%= i %>, !- Name + Autosize, !- Reference Capacity {W} + <%= chiller_cop %>, !- Reference COP {} + <%= chw_temp_ref %>, !- Reference Leaving Chilled Water Temperature {C} + <%= cw_temp_ref %>, !- Reference Leaving Condenser Water Temperature {C} + <%= design_flow %>, !- Reference Chilled Water Flow Rate {m3/s} + Autosize, !- Reference Condenser Fluid Flow Rate {m3/s} + <%= name %> Chiller Cap Curve, !- Cooling Capacity Function of Temperature Curve Name + <%= name %> Chiller EIR Curve, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name + <%= name %> Chiller PLR Curve, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name + 0.15, !- Minimum Part Load Ratio {} + 1.0, !- Maximum Part Load Ratio {} + 0.8, !- Optimum Part Load Ratio {} + 0.15, !- Minimum Unloading Ratio {} + <%= name %> Chiller <%= i %> Inlet Node, !- Chilled Water Inlet Node Name + <%= name %> Supply Equipment Outlet Node <%= i %>, !- Chilled Water Outlet Node Name + <%= name %> Chiller <%= i %> Water Inlet Node, !- Condenser Inlet Node Name + <%= name %> Chiller <%= i %> Water Outlet Node, !- Condenser Outlet Node Name + WaterCooled, !- Condenser Type + , !- Condenser Fan Power Ratio {W/W} + 1.0, !- Fraction of Compressor Electric Consumption Rejected by Condenser {} + 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} + <%= chiller_flow_mode %>, !- Chiller Flow Mode + 0.0, !- Design Heat Recovery Water Flow Rate {m3/s} + , !- Heat Recovery Inlet Node Name + , !- Heat Recovery Outlet Node Name + <%= chiller_sizing %>; !- Sizing Factor + +Branch, + <%= name %> <%= i %> HR Demand Branch, !- Name + , !- Pressure Drop Curve Name + Chiller:Electric:EIR, !- Component 1 Object Type + <%= name %> Chiller <%= i %>, !- Component 1 Name + <%= name %> Chiller <%= i %> Water Inlet Node, !- Component 1 Inlet Node Name + <%= name %> Chiller <%= i %> Water Outlet Node; !- Component 1 Outlet Node Name + + <% end %> <% else %> +! If chiller condenser is aircooled Chiller:Electric:EIR, <%= name %> Chiller <%= i %>, !- Name Autosize, !- Reference Capacity {W} @@ -595,7 +660,6 @@ Chiller:Electric:EIR, , !- Heat Recovery Outlet Node Name <%= chiller_sizing %>; !- Sizing Factor - OutdoorAir:Node, <%= name %> Chiller <%= i %> Condenser Inlet Node; !- Name @@ -1913,6 +1977,188 @@ Curve:Bicubic, 36.52, !- Maximum Value of x 0.19, !- Minimum Value of y 1.03; !- Maximum Value of y + +! Solaris(Behzad S. Rizi) - 2024-08-09 Added water-cooled centrifugal chiller performance curves as the basecase >>> ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD +<% elsif (chiller_model == "WC Cent Carrier 19XR 1234kW/5.39COP/VSD") %> + +Curve:Biquadratic, + <%= name %> Chiller Cap Curve, !- Name + 5.905815E-01, !- Coefficient1 Constant + 1.190927E-01, !- Coefficient2 x + -6.727309E-03, !- Coefficient3 x**2 + -9.580836E-03, !- Coefficient4 y + -3.034704E-04, !- Coefficient5 y**2 + 1.540686E-03, !- Coefficient6 x*y + 7.22, !- Minimum Value of x + 12.78, !- Maximum Value of x + 12.78, !- Minimum Value of y + 26.67; !- Maximum Value of y + +Curve:Biquadratic, + <%= name %> Chiller EIR Curve, !- Name + 3.771659E-01, !- Coefficient1 Constant + 1.144965E-01, !- Coefficient2 x + -8.186893E-03, !- Coefficient3 x**2 + -3.372584E-03, !- Coefficient4 y + 1.689440E-04, !- Coefficient5 y**2 + 1.008523E-03, !- Coefficient6 x*y + 7.22, !- Minimum Value of x + 12.78, !- Maximum Value of x + 12.78, !- Minimum Value of y + 26.67; !- Maximum Value of y + + Curve:Quadratic, + <%= name %> Chiller PLR Curve, !- Name + 1.495681E-01, !- Coefficient1 Constant + -1.449639E-01, !- Coefficient2 x + 9.941070E-01, !- Coefficient3 x**2 + 0.19, !- Minimum Value of x + 1.02; !- Maximum Value of x + +! Solaris(Behzad S. Rizi) - 2024-08-22 Added water-cooled centrifugal chiller performance curves as the basecase >>> ReformEIRChiller Carrier 19XR 1234kW/5.39COP/VSD +<% elsif (chiller_model == "ReformEIRChiller WC Cent Carrier 19XR 1234kW/5.39COP/VSD") %> + + Curve:Biquadratic, + <%= name %> Chiller Cap Curve, !- Name + 6.134255E-01, !- Coefficient1 Constant + 1.092476E-01, !- Coefficient2 x + -7.352739E-03, !- Coefficient3 x**2 + -2.589985E-03, !- Coefficient4 y + -3.793512E-04, !- Coefficient5 y**2 + 1.839978E-03, !- Coefficient6 x*y + 7.22, !- Minimum Value of x + 12.78, !- Maximum Value of x + 22.24, !- Minimum Value of y + 36.28; !- Maximum Value of y + +! +! Energy Input to Cooling Output Ratio Function of Temperature Curve +! x = Leaving Chilled Water Temperature and y = Leaving Condenser Water Temperature + + Curve:Biquadratic, + <%= name %> Chiller EIR Curve, !- Name + 4.746375E-01, !- Coefficient1 Constant + 9.120326E-02, !- Coefficient2 x + -7.295060E-03, !- Coefficient3 x**2 + -5.662273E-03, !- Coefficient4 y + 1.928027E-04, !- Coefficient5 y**2 + 8.244779E-04, !- Coefficient6 x*y + 7.22, !- Minimum Value of x + 12.78, !- Maximum Value of x + 22.24, !- Minimum Value of y + 36.28; !- Maximum Value of y + +! +! Energy Input to Cooling Output Ratio Function of Part Load Ratio Curve +! x = Leaving Condenser Water Temperature and y = Part Load Ratio (load/capacity) + + Curve:Bicubic, + <%= name %> Chiller PLR Curve, !- Name + 1.207212E-01, !- Coefficient1 Constant + -9.914826E-03, !- Coefficient2 x + 1.854918E-05, !- Coefficient3 x**2 + 9.880331E-01, !- Coefficient4 y + -8.955866E-01, !- Coefficient5 y**2 + 8.894574E-03, !- Coefficient6 x*y + 0.000000E+00, !- Coefficient7 x**3 + 8.005552E-01, !- Coefficient8 y**3 + 0.000000E+00, !- Coefficient9 x**2*y + 0.000000E+00, !- Coefficient10 x*y**2 + 14.38, !- Minimum Value of x + 34.99, !- Maximum Value of x + 0.19, !- Minimum Value of y + 1.02; !- Maximum Value of y + +! Solaris(Behzad S. Rizi) - 2024-08-09 Added water-cooled screw chiller performance curves as the basecase >>> ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve +<% elsif (chiller_model == "Screw WC Trane RTHB 1051kW/5.05COP/Valve") %> + +Curve:Biquadratic, + <%= name %> Chiller Cap Curve, !- Name + 9.482157E-01, !- Coefficient1 Constant + 3.306737E-02, !- Coefficient2 x + -6.450072E-05, !- Coefficient3 x**2 + -3.756522E-03, !- Coefficient4 y + -6.501672E-05, !- Coefficient5 y**2 + 2.517986E-15, !- Coefficient6 x*y + 4.44, !- Minimum Value of x + 8.89, !- Maximum Value of x + 23.89, !- Minimum Value of y + 35.00; !- Maximum Value of y + +Curve:Biquadratic, + <%= name %> Chiller EIR Curve, !- Name + 4.904181E-01, !- Coefficient1 Constant + -5.530317E-03, !- Coefficient2 x + 1.209907E-03, !- Coefficient3 x**2 + 9.122333E-03, !- Coefficient4 y + 5.923591E-04, !- Coefficient5 y**2 + -1.469958E-03, !- Coefficient6 x*y + 4.44, !- Minimum Value of x + 8.89, !- Maximum Value of x + 23.89, !- Minimum Value of y + 35.00; !- Maximum Value of y + +Curve:Quadratic, + <%= name %> Chiller PLR Curve, !- Name + 2.590465E-01, !- Coefficient1 Constant + 2.148987E-01, !- Coefficient2 x + 5.265039E-01, !- Coefficient3 x**2 + 0.20, !- Minimum Value of x + 1.01; !- Maximum Value of x + +! Solaris(Behzad S. Rizi) - 2024-08-22 Added water-cooled screw chiller performance curves as the basecase >>> ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve +<% elsif (chiller_model == "ReformEIRChiller Screw WC Carrier 23XL 1062kW/5.50COP/Valve") %> + +Curve:Biquadratic, + <%= name %> Chiller Cap Curve, !- Name + 1.054485E+00, !- Coefficient1 Constant + 1.015650E-02, !- Coefficient2 x + -4.899041E-03, !- Coefficient3 x**2 + -3.792726E-03, !- Coefficient4 y + -3.699876E-04, !- Coefficient5 y**2 + 2.891276E-03, !- Coefficient6 x*y + 6.67, !- Minimum Value of x + 10.00, !- Maximum Value of x + 26.44, !- Minimum Value of y + 35.10; !- Maximum Value of y + +! +! Energy Input to Cooling Output Ratio Function of Temperature Curve +! x = Leaving Chilled Water Temperature and y = Leaving Condenser Water Temperature + + Curve:Biquadratic, + <%= name %> Chiller EIR Curve, !- Name + 1.369592E-01, !- Coefficient1 Constant + -5.681693E-03, !- Coefficient2 x + 2.795150E-04, !- Coefficient3 x**2 + 2.407603E-02, !- Coefficient4 y + 2.142516E-04, !- Coefficient5 y**2 + -8.850727E-04, !- Coefficient6 x*y + 6.67, !- Minimum Value of x + 10.00, !- Maximum Value of x + 26.44, !- Minimum Value of y + 35.10; !- Maximum Value of y + +! +! Energy Input to Cooling Output Ratio Function of Part Load Ratio Curve +! x = Leaving Condenser Water Temperature and y = Part Load Ratio (load/capacity) + + Curve:Bicubic, + <%= name %> Chiller PLR Curve, !- Name + 1.385765E+00, !- Coefficient1 Constant + -3.549685E-02, !- Coefficient2 x + -4.110930E-06, !- Coefficient3 x**2 + -7.678018E-01, !- Coefficient4 y + 7.228808E-01, !- Coefficient5 y**2 + 3.573245E-02, !- Coefficient6 x*y + 0.000000E+00, !- Coefficient7 x**3 + -3.442173E-01, !- Coefficient8 y**3 + 0.000000E+00, !- Coefficient9 x**2*y + 0.000000E+00, !- Coefficient10 x*y**2 + 30.60, !- Minimum Value of x + 34.70, !- Maximum Value of x + 0.20, !- Minimum Value of y + 1.01; !- Maximum Value of y <% elsif (chiller_model == "WC PD 2010 B") %> @@ -2004,6 +2250,126 @@ Curve:Bicubic, 0.19, !- Minimum Value of y 1.03; !- Maximum Value of y +! Solaris - 2024-06-12 Added water-cooled chiller performance curves(Chiller:Electric:ReformulatedEIR) +! Model 7 performance curves for 12% Path B PLE improvement +<% elsif (chiller_model == "Model 7 WC Chiller") %> +Curve:Biquadratic, + <%= name %> Chiller Cap Curve, !- Name + 0.989616849, !- Coefficient1 Constant + 0.029621942, !- Coefficient2 x + 0.000137363, !- Coefficient3 x**2 + -0.007781822, !- Coefficient4 y + 0.000103918, !- Coefficient5 y**2 + -0.00020792, !- Coefficient6 x*y + 0, !- Minimum Value of x + 100, !- Maximum Value of x + 0, !- Minimum Value of y + 100, !- Maximum Value of y + 0, !- Minimum Curve Output + 1.5; !- Maximum Curve Output + +Curve:Biquadratic, + <%= name %> Chiller EIR Curve, !- Name + 0.544578782, !- Coefficient1 Constant + -0.011128038, !- Coefficient2 x + 0.00061257, !- Coefficient3 x**2 + 0.000848405, !- Coefficient4 y + 0.0005857, !- Coefficient5 y**2 + -0.000966413, !- Coefficient6 x*y + 0, !- Minimum Value of x + 100, !- Maximum Value of x + 0, !- Minimum Value of y + 100, !- Maximum Value of y + 0, !- Minimum Curve Output + 1.5; !- Maximum Curve Output + +Curve:ChillerPartLoadWithLift, + <%= name %> Chiller PLR Curve, !- Name + 0.162615058, !- Coefficient1 C1 + -0.843913483, !- Coefficient2 C2 + 0.283449427, !- Coefficient3 C3 + -0.078715236, !- Coefficient4 C4 + 0.394265877, !- Coefficient5 C5 + 1.100071665, !- Coefficient6 C6 + 0.000000E+00, !- Coefficient7 C7 + 0.000000E+00, !- Coefficient8 C8 + 0.000000E+00, !- Coefficient9 C9 + 0.000000E+00, !- Coefficient10 C10 + 0.000000E+00, !- Coefficient11 C11 + 0.000000E+00, !- Coefficient12 C12 + 0.36, !- Minimum Value of x + 1.08, !- Maximum Value of x + 0.1, !- Minimum Value of y + 1, !- Maximum Value of y + -0.035, !- Minimum Value of z + 0.3144, !- Maximum Value of z + , !- Minimum Curve Output + , !- Maximum Curve Output + Dimensionless, !- Input Unit Type for x + Dimensionless, !- Input Unit Type for y + Dimensionless, !- Input Unit Type for z + Dimensionless; !- Output Unit Type + +! Solaris - 2024-06-12 Added water-cooled chiller performance curves(Chiller:Electric:ReformulatedEIR) +! Model 9 performance curves for 17% Path B PLE improvement +<% elsif (chiller_model == "Model 9 WC Chiller") %> +Curve:Biquadratic, + <%= name %> Chiller Cap Curve, !- Name + 1.833870, !- Coefficient1 Constant + -0.018299, !- Coefficient2 x + 0.004437, !- Coefficient3 x**2 + -0.054290, !- Coefficient4 y + 0.000876, !- Coefficient5 y**2 + -0.000356, !- Coefficient6 x*y + 0, !- Minimum Value of x + 100, !- Maximum Value of x + 0, !- Minimum Value of y + 100, !- Maximum Value of y + 0, !- Minimum Curve Output + 1.5; !- Maximum Curve Output + +Curve:Biquadratic, + <%= name %> Chiller EIR Curve, !- Name + 1.097221, !- Coefficient1 Constant + -0.013698, !- Coefficient2 x + 0.001890, !- Coefficient3 x**2 + -0.031726, !- Coefficient4 y + 0.001072, !- Coefficient5 y**2 + -0.001329, !- Coefficient6 x*y + 0, !- Minimum Value of x + 100, !- Maximum Value of x + 0, !- Minimum Value of y + 100, !- Maximum Value of y + 0, !- Minimum Curve Output + 1.5; !- Maximum Curve Output + +Curve:ChillerPartLoadWithLift, + <%= name %> Chiller PLR Curve, !- Name + 0.087760714, !- Coefficient1 C1 + -0.214192565, !- Coefficient2 C2 + 0.277130448, !- Coefficient3 C3 + -0.111975778, !- Coefficient4 C4 + 0.31630787, !- Coefficient5 C5 + 0.629734788, !- Coefficient6 C6 + 0.000000E+00, !- Coefficient7 C7 + 0.000000E+00, !- Coefficient8 C8 + 0.000000E+00, !- Coefficient9 C9 + 0.000000E+00, !- Coefficient10 C10 + 0.000000E+00, !- Coefficient11 C11 + 0.000000E+00, !- Coefficient12 C12 + 0.35, !- Minimum Value of x + 1.08, !- Maximum Value of x + 0.1, !- Minimum Value of y + 1, !- Maximum Value of y + -0.035, !- Minimum Value of z + 0.3144, !- Maximum Value of z + , !- Minimum Curve Output + , !- Maximum Curve Output + Dimensionless, !- Input Unit Type for x + Dimensionless, !- Input Unit Type for y + Dimensionless, !- Input Unit Type for z + Dimensionless; !- Output Unit Type + <% elsif (chiller_model == "WC PD 2010 A Large") %> Curve:Biquadratic,